期刊文献+

故障测距中的参数误差归算修正算法 被引量:2

Parameter errors converting and correcting algorithm for fault location
在线阅读 下载PDF
导出
摘要 在输电线路故障测距中,线路参数变化或其他参数误差都会对测距精度有较大的影响。针对基于分布参数模型的双端不同步数据故障测距问题,提出了一种参数误差归算修正算法。该算法将各类参数误差归算为单位长度线路参数的变化,利用故障前电压/电流数据,计算出归算系数,反馈修正系统模型。Matlab仿真表明,该算法能有效地减少各类参数误差的影响,提高了故障测距的抗干扰能力和故障测距精度。 In the transmission line fault location, transmission line parameters changes or other parameter errors impact greatly on the accuracy of fault location. For fault location of the two-terminal non-synchronous data based on distribution parameters model, a parameter errors converting and correcting algorithm was presented. The different parameter errors were converted to unit length parameter changes of the transmission line. Using the two-terminal data of voltage and current before fault time, the convert coefficient was calculated. Then system model was feedback amended. Matlab simulation result shows that this algorithm can effectively reduce the various parameter errors impact, improve anti-jamming capability and accuracy of fault location.
出处 《机电工程》 CAS 2010年第4期104-107,共4页 Journal of Mechanical & Electrical Engineering
关键词 故障测距 参数误差 归算系数 抗干扰能力 fault location parameter errors convert coefficient anti-jamming capability
  • 相关文献

参考文献6

二级参考文献24

  • 1黄雄,王志华,尹项根,张哲.高压输电线路行波测距的行波波速确定方法[J].电网技术,2004,28(19):34-37. 被引量:93
  • 2钱峰,陈义飞,龚庆武.一种新型双端时域故障定位算法[J].高电压技术,2005,31(2):81-83. 被引量:3
  • 3Kezunovic M, Mrkic J.An, Accurate Fault Location Algorithm Using Synchronized Sampling[J]. Electric Power Systems Research, 1994,(29): 161-169.
  • 4Johns A T, Jamali S, Accurate Fault Location Technique for Power Transmission Lines [ J]. IEEE Proc, Vol. 137, Pt. C,No.6, Nov. 1990.
  • 5Girgis A A, Hart D G, et al. A New Fault Location Technique for Two and Three-Terminal Lines[J]. IEEE Trans on PWRD,Vol.7,No. 1 Jan. 1992.
  • 6Bo Z Q, Weller G, Jiang F, et al. Application of GPS Based Fault Location Scheme for Distribution System [A].International Conference on Power System Technology Proceeding. Beijing: 1998.
  • 7Jiang J A, Yang J Z, Lin Y H, et al. An adaptive PMU based fault detection/location technique for transmission lines-Part I: Theroy and algorithms[J]. IEEE Trans on Power Delivery, 2000, 15(2): 486-493.
  • 8Chen C S, Liu C W, Jiang J A. A new adaptive PMU based protection scheme for transposed/untransposed parallel transmission lines[J]. IEEE Trans on Power Delivery, 2002, 17(2) : 395-404.
  • 9Kezunovic M, Mrkic J, Perunicic B. An accurente fault location algorithm using synchronized sampling E J3. Electric Power Systems Research,1994, 29(1):161-169.
  • 10Novosel D, Hart D G, Udren E, et al. Unsynchronized two-terminal fault location estimation[J]. IEEE Trans on Power Delivery, 1996, 11(1):130-138.