摘要
在非全相运行期间,由于保护逻辑设置不当或通道等因素的影响,往往会导致高压输电线路纵联零序方向保护误动作。结合现场500kV电网中出现的某次故障事故,深入分析了事故中纵联零序方向保护误动作的原因:通信接口设备对允许信号的展宽;非全相运行时没有闭锁纵联零序保护。并详细描述了影响纵联零序方向保护正确动作的主要因素,有弱馈、非全相运行、分布电容、功率倒向、零序互感等。给出了防止纵联零序方向保护误动作的解决措施:非全相运行与零序功率倒向、逻辑的输出通过或门构成闭锁纵联零序保护;去掉接口装置对允许信号的展宽。现场运行结果证明了该解决措施的准确性和有效性。
If the protective logic setting is incorrect or the communication channel wrong,the longitudinal zero sequence direction protection of high voltage transmission line will operate improperly under non-complete phase operating condition. With an accident in 500 kV power network,an improper operation of the longitudinal zero sequence direction protection is analyzed:the enable signal is extended by the communication interface device and the longitudinal zero sequence protection is not blocked under non-complete phase operation. The main factors causing its improper operation are described in detail,i.e, week feeding , non- complete operation, distributed capacitance, inverse power direction,zero sequence mutual inductance,etc.. The countermeasures are put forward: blocking the longitudinal zero sequence direction ,protection by the OR gate output of the non-complete operation signal and inverse zero sequence power signal;removing the interface device to prevent extension of enable signal. Site operation shows that proposed countermeasures are correct and effect.
出处
《电力自动化设备》
EI
CSCD
北大核心
2007年第7期122-125,共4页
Electric Power Automation Equipment
关键词
输电线路
纵联保护
零序
误动作
transmission line
longitudinal protection
zero sequence
misoperation