期刊文献+

矿井高压电网漏电保护装置动作参数分析 被引量:10

An analysis of the tripping parameters of earth-leakage protection devices for high-voltage electric network in mines
在线阅读 下载PDF
导出
摘要 对于中性点不接地的矿井高压电网,漏电保护装置的零序电压动作值是其重要技术数据之一.当其整定值确定之后,漏电保护装置的漏电动作电阻值(R)及其相关的电网每相对地电容值(C),即可由本文所给的简化计算公式求得.该公式是在忽略绝缘电阻(r)的条件下求得的.在实际电网中使用,计算误差不大.该方法便于现场根据实测的绝缘参数变化范围进行调节. For an ungroundedneutral highvoltage electric network in mines, the tripping value of zerosequence voltage of the earthleakage protection devices is one of its important technical data. When it is set up, the tripping leakage resistance (R) and corresponding capacitance of the network to the ground per phase (C) can be calculated by the simplified formula presented in this paper in the condition of neglecting the insulance to the ground (r). Owing to the fact that the error of calculation for the real network is not very big, this method can be easily used in practice, especially for a range of measured insulation parameters of the power system.
出处 《煤炭学报》 EI CAS CSCD 北大核心 2003年第2期205-209,共5页 Journal of China Coal Society
基金 国家自然科学基金资助项目(50077022)
关键词 矿井 高压电网 漏电保护装置 中性点不接地 零序电压 power system in mines earth-leakage protection tripping values of parameters