期刊文献+

煤矿谐振接地系统暂态脉冲特征研究 被引量:2

Research of characteristics of transient pulse in coal mine resonant grounding system
在线阅读 下载PDF
导出
摘要 通过推导煤矿单变电所和多变电所模式下谐振接地系统发生单相接地故障时各支路故障时刻的零序电流表达式,分析了故障线路与非故障线路的暂态脉冲极性关系,以及暂态脉冲的幅度及脉冲宽度与接地电阻、线路对地分布电容和故障时刻之间的关系,并给出了相应的表达式。故障线路的暂态脉冲幅度最大且极性与非故障线路的暂态脉冲极性相反;故障时刻暂态脉冲的幅度与接地电阻成反比,与故障时刻故障相的相位角正弦值成正比;所有非故障线路的暂态脉冲宽度一致,且小于故障线路的暂态脉冲宽度,暂态脉冲宽度与接地电阻成正比。Matlab/Simulink仿真实验验证了理论分析的正确性。 By means of deduction of zero-sequence current expressions when single-phase grounding fault occurs in single substation mode and multi-substation mode of coal mine resonant grounding system, polarity relationship between transient pulse of fault line and normal line, and relationships among amplitude or width of transient pulse, grounding resistance, shunt capacitance and fault time were analyzed, and corresponding expressions were given. Polarity of transient pulse of fault line is opposite to the ones of normal lines, and amplitude of the transient pulse of fault line is the largest among all lines. The amplitude of transient pulse at the fault time is inversely proportional to grounding resistance and proportional to sin of angle of fault phase. All the normal lines have the same width of transient pulse, which is smaller than the one of the fault line, and the width of transient pulse is proportional to the grounding resistance. The Matlab/Simulink simulation proves correctness of above theoretical conclusions.
作者 王晋宏
出处 《工矿自动化》 北大核心 2014年第7期61-67,共7页 Journal Of Mine Automation
关键词 煤矿供电系统 变电所 谐振接地系统 单相接地故障 暂态脉冲 脉冲极性 power supply of coal mine substation resonant grounding system single-phasegrounding fault transient pulse pulse polarity
  • 相关文献

参考文献14

  • 1ZHANG X H, HA H X, PAN Z C, et al. Grounding faulty line selection in non-solidly grounded systems using transient energy [C]// International Power Engineering Conference, Singapore, 2007: 1147-1150.
  • 2HUANG S J, HSIEH C T. High-impedance fault detection utilizing a Morlet wavelet transform approach[J].IEEE Transactions on Power Delivery, 1999, 14(4): 1401-1410.
  • 3CHAARI O, MEUNIER M, BROUAYE F. Wavelets: a new tool for the resonant grounded power distribution systems relaying [J].IEEE Transactions on Power Delivery, 1996, 11(3) : 1301- 1308.
  • 4田书,何金朋,聂赫.基于暂态零序能量的配电网故障选线方法研究[J].工矿自动化,2012,38(1):51-54. 被引量:8
  • 5STURE L. Sensitive earth fault protection for MV distribution system[C]//International Conference on Electricity Distribution, Liege, 1991 : 184-188.
  • 6龚静,李英姿,王亚慧.基于DSP的小电流接地系统暂态首半波法实现[J].电工技术,2006(9):34-36. 被引量:16
  • 7郗来迎,王崇林,布朋生,彭杨.基于首半波与有功分量的综合选线装置[J].煤矿机械,2008,29(8):114-116. 被引量:13
  • 8吴艳辉.基于零序电流基波暂态分量极性的小电流单相接地故障选线方法[C]//中国高等学校电力系统及其自动化专业第24届学术年会论文集:中册,北京,2008:1532-1535.
  • 9薛永端,冯祖仁,徐丙垠,陈羽,李京.基于暂态零序电流比较的小电流接地选线研究[J].电力系统自动化,2003,27(9):48-53. 被引量:229
  • 10XUE Yongduan, XU Bingyin, CHEN Yu, et al. Earth fault protection using transient signals in non- solid earthed network [C ]//Proceedings ofInternational Conference on Power System Technology, Kunming, 2002: 1763-1767.