摘要
以某300 MW压缩空气储能电站空气压缩机组为依托,开展了机组刚性框架基础的动力性能试验研究,并分别与不考虑和考虑地基刚度影响的数值仿真计算结果进行对比。结果表明:300 MW空气压缩机组刚性框架基础具有良好的动力性能,振动位移峰值满足我国规范限值要求;以柱底固结模型进行计算指导结构设计是偏于安全的,但在评估高低频组合扰力作用的基础动力性能时,应考虑地基刚度的影响。研究成果可为高低频组合扰力作用的动力机器基础设计及相关工程应用提供参考。
The experimental study on the dynamic performance of rigid frame foundation of air compressor unit is carried out in this paper based on a 300 MW compressed air energy storage power station.The test results are compared with the numerical simulation results of the column bottom consolidation model and the numerical simulation results considering the influence of foundation stiffness.The results showed that the rigid frame foundation of the 300 MW air compressor unit has good dynamic performance,and the peak vibration displacement meets the limit requirements of Chinese regulations.Using the finite element analysis model with column bottom consolidation can guide structural design,but the influence of foundation stiffness should be considered when the dynamic performance of the foundation forced by high and low frequency combined disturbance is evaluated.The research results can provide reference for the design of air compressor unit foundations under high and low frequency combined disturbance effects.
作者
朱斌
陈伊军
周兴乐
王浩
岳方方
杜林林
ZHU Bin;CHEN Yijun;ZHOU Xingle;WANG Hao;YUE Fangfang;DU Linlin(Central South China Electric Power Design Institute Co.,Ltd.,China Power Engineering Consulting Group,Wuhan 430071,China;SINOMACH Engineering Vibration Control Technology Research Center,SINOMACH Academy of Seience and Technology Co.,Ltd.,Beijing 100080,China)
出处
《武汉大学学报(工学版)》
CSCD
北大核心
2024年第S1期58-64,共7页
Engineering Journal of Wuhan University
关键词
压缩空气储能
空气压缩机组
高低频扰力
动力性能
模型试验
compressed air energy storage power station
air compressor unit
high and low frequency disturbing force
dynamic performance
scale model test