主变冷却器风机全停PLC回路故障分析 被引量:1

Fault Analysis of PLC Circuit for Complete Shutdown of Main Transformer Cooler Fan
在线阅读 下载PDF
导出
摘要 针对某变电站主变冷却器风机全停的异常现象进行了研究,结合PLC二次回路图纸,分析了故障点并查找出异常现象产生的原因,由于冷却器手动/自动启动控制回路电源均取自电源变送器输出的301回路,导致当电源变送器故障时,301回路失电,K6、K7线圈失电,造成多功能保护开关被关断,所以第一组风机多功能保护开关BQ1处于停止位置,而第二组风机多功能保护开关BQ2可能由于关断瞬间冲击电流过大或本身元器件老化损坏,提出了改进提升的措施,建议设计人员应该采用2台变送器进行供电等处理方法,希望能引起设计人员足够的重视,在PLC二次回路设计时避免类似问题。 The abnormal phenomenon of total shutdown of cooler fan of main transformer in a substation is studied.Combined with the drawing of PLC secondary circuit,the fault points are analyzed and the causes of abnormal phenomena are found out.Since the power supply of the manual/automatic start control loop of the cooler is from loop 301 output by the power transmitter,when the power transmitter fails,loop 301 loses power.K6 and K7 coils lost power,causing the multi-function protection switch to be turned off.Therefore,the multifunctional protection switch bq1 of the first group of fans is in the stop position.The multifunctional protection switch BQ2 of the second group of fans may be damaged due to excessive impulse current at the moment of shutdown or aging of its own components.This paper puts forward some measures to improve the lifting,and suggests that designers should use two transmitters for power supply and other treatment methods.It is hoped that designers can pay enough attention to avoid similar problems in the design of PLC secondary circuit.
作者 江鸿翔 陈秀兰 叶心舒 JIANG Hongxiang;CHEN Xiulan;YE Xinshu(Super high voltage branch of State Grid Fujian Electric Power Co.,Ltd.,Fujian Fuzhou 350000;Material branch of State Grid Fujian Electric Power Co.,Ltd.,Fujian Fuzhou,350000)
出处 《农村电气化》 2022年第6期25-27,共3页 Rural Electrification
关键词 冷却器 多功能保护开关 可编程逻辑控制器故障 cooler multifunctional protection switch programmable logic controller fault
  • 相关文献

参考文献3

二级参考文献9

共引文献13

同被引文献1

引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部