摘要
运用 FDS 模拟在特定机械排烟量下地下商场发生火灾时,观察不同细水雾喷头间距对火场烟气的控制影响。分析得到,在5 MW火灾功率下,排烟量60 m^3/(h·m^2)时,喷头间距2.0 m灭火效果较好,对大空间消防设计中喷头间距3.0 m更经济。
Using FDS simulation, under specific quantity of mechanical smoke exhaust, the effect of different spacing of water mist sprinkler on the fire smoke control was observed in case of a fire occurs in underground mall. From the analysis result, under the condition of fire power is 5 MW, smoke exhaust volume is 60 m^3/(h m^2), nozzle spacing is 2.0 m, the extinguishing effect is best, the design of fire protection in large space with sprinkler spacing of 3.0 m is more economic.
出处
《城市建筑》
2014年第18期237-237,共1页
Urbanism and Architecture
关键词
火灾
细水雾
喷头间距
fire
water mist
sprinkler spacing