期刊文献+

应用于三相并网逆变器的PR解耦控制器 被引量:9

PR-decouple Controller Applied in Three-phase Grid-connected lnverters
在线阅读 下载PDF
导出
摘要 提出一种用于三相并网逆变器的控制算法,称为比例谐振(PR)解耦控制器。该控制器在两相静止坐标系下实现,控制方程式包括比例项、谐振项、解耦项及电网电压前馈项。谐振项作为普通谐振控制器的改进,能使所提出的控制器具有无静差的稳态性能,并且以一个二阶离散状态方程,替代了传统谐振控制所需的两个二阶差分方程,更易于在实时数字处理系统中实现。解耦项是矢量控制中有功、无功电流解耦控制功能在静止坐标系下的实现。最后通过实验验证了该控制器的优良性能。 A controller named as proportion resonant(PR) decouple for three-phase grid-connected inverters is pre- sented.It is implemented in two-phase static frame and includes four items:proportion,resonant,decouple and gird voltage feedforward.The resonance item,as an improvement of classical resonant controller,makes the proposed controller no static difference, and replaces two second order deference equations by a second order discrete state equation which is more feasible in practical digital signal processing system.The decouple item in stationary frame realizes independent regulation of active and reactive current, which is the same as vector control.Experimental results show that the proposed algorithm has good performance.
出处 《电力电子技术》 CSCD 北大核心 2013年第4期14-16,共3页 Power Electronics
关键词 控制器 比例谐振 解耦 逆变器 controller proportion resonant decouple inverter
  • 相关文献

参考文献5

  • 1D Zmood, D Holmes, G Bode.Frequency Domain Analysis of Three-phase Linear Current Regulator[J].IEEE Trans. Ind. Appl., 2001,37 (2) : 601-610.
  • 2R Teodorescu, F Blaabjerg, Liserre M.Proportional Reso- nant Controllers and Filters for Grid-connected Voltage- source Converters[A].IEEE Proceedings of Electric Pow- er Applications[C].2006 : 750-762.
  • 3F Wang, M Benhabib, J Duarte.Sequence Decoupled Res- onant Controller for Three-phase Grid-connected Invert- ers[A].Proceedings of IEEE APEC[C].2009 : 121-127.
  • 4马海啸.一种新颖的比例积分谐振控制策略[J].电力电子技术,2011,45(6):73-75. 被引量:11
  • 5张兴,曹仁贤.太阳能光伏发电及其逆变控制[M].北京:机械工业出版社,2010.

二级参考文献5

共引文献10

同被引文献71

  • 1白志红,阮新波,徐林.基于LCL滤波器的并网逆变器的控制策略[J].电工技术学报,2011,26(S1):118-124. 被引量:30
  • 2张兴,张崇巍.PWM整流器及其控制[M].北京:机械工业出版社.2012.
  • 3YEPES A G, FREIJEDO F D, LOPEZ O, et al. High-perfor- mance digital resonant controllers implemented with two inte- grators [J]. IEEE Transactions on Power Electronics, 2011, 2: 563-576.
  • 4KELLER J P, ANDERSON B D O. A new approach to the dis- cretization of continuous-time controllers [C]// American Con- trol Conference. USA: IEEE, 1990: 1127-1133.
  • 5R Teodorescu, F Blaahjerg, Liserre M. Proportional Resonant Controllers and Filters for "Grid - connected Voltage - :urce Converters[ A]. IEEE Proceedings of Electric Power Applications[ C ]. 2006:750 -762.
  • 6F Wang, M Benhabib, J Duarte. Sequence Decoupled Resonant Con- troller for Three - phase Grid - connected lnverters[ A ]. Proceedings of IEEE APEC[ C]. 2009 : 121 - 127.
  • 7Liserre M, Teodorescu R, Blaabjerg F. Stability ofphotovoltaic and wind turbine grid-connected inverters for a large set of grid impedance values[J]. IEEE Transactions on Power Electronics, 2006, 21(1): 263-272.
  • 8Agorreta J L, Borrega M, Lopez J, et al. Modeling and control of N-paralleled grid-connected inverters with LCL filter coupled due to grid impedance in PV plants[J]. IEEE Transactions on Power Electronics, 2011, 24(3): 770-785.
  • 9Cespedes M, Sun J. Renewable energy systems instability involving grid-parallel inverters[C]//Applied Power Electronics Conference and Exposition. Washington: IEEE, 2009: 1971-1977.
  • 10Enslin J H R, Heskes P J M. Harmonic imeraction between a large number of distributed power inverters and the distribution network[J]. IEEE Transactions on Power Electronics, 2004, 19(6): 1586-1593.