期刊文献+

基于小波去噪的冷水机组传感器故障检测 被引量:21

Chiller sensor fault detection using wavelet de-noising
原文传递
导出
摘要 对基于主元分析方法的冷水机组传感器故障检测效率取决于训练数据和被测数据的质量的问题进行了研究.采用小波变换剔除测量数据中的噪声,提高数据质量,从而提高故障检测效率.结果表明:在-1.0℃故障下,基于小波去噪的主元分析方法的故障检测效率达到了91%.在同等数值的正负偏差故障下,基于小波去噪的主元分析方法的故障检测效率对称性更好.故障检测效率与小波基函数的分解层次关系密切.分解层次越多,故障检测效率越高.所有的db族小波基函数在5层分解的情况下,-0.5℃故障下的检测效率均能达到90%以上. Chiller sensor fault detection based on principal component analysis is a data-based analysis method. The fault detection efficiency relies on the quality of the training data and the measured data. The measurement noise was removed by wavelet transfer. The fault detection efficiencies were promoted because of the promotion of the data quality. Results show that the fault detection efficiency is 91G on the --1.0 ℃ introduced fault level by the PCA-based method combined with wavelet de-noising. On the same values of the positive and negative fault levels, the symmetry of the presented method is well than the normal PCA-based method. The fault detection efficiencies rely on the decomposed layer of the wavelet transfer. The more decomposed layers are, the well the fault detection efficiencies are. On the --0.5 ℃ fault level, the fault detection efficiencies of all the db's wavelet function on the 5 layers decomposition are greater than 90%.
出处 《华中科技大学学报(自然科学版)》 EI CAS CSCD 北大核心 2013年第3期16-19,24,共5页 Journal of Huazhong University of Science and Technology(Natural Science Edition)
基金 国家科技支撑计划资助项目(2008BAJ12B03) 供热供燃气通风及空调工程北京市重点实验室研究基金资助课题(NR2012K06) 2010年度湖北省建设科技项目 2011年度湖北省建设科技项目
关键词 主元分析 小波变换 传感器 故障检测 噪声 冷水机组 principal component analysis wavelet transform sensor fault detection noise chiller
  • 相关文献

参考文献15

  • 1Katipamula S, Brambley M R. Methods for fault de- tection, diagnostics, and prognostics for building sys- tems-a review, part I [J]. HVACgaR Research, 2005, 11(1): 3-25.
  • 2Wang S W, Cui J T. Sensor-fault detection, diagno- sis and estimation for centrifugal chiller systems using principal-component analysis method [J ]. Applied Energy, 2005, 82(3) : 197-213.
  • 3Hu Y P, Chen H X, Xie J L, et al. Chiller sensor fault detection using a self-adaptive principal compo- nent analysis method [J]. Energy and Buildings, 2012, 54: 252-258.
  • 4Chen Y M, Lan L L. A fault detection technique for air-source heat pump water chiller/heaters[J]. Ener- gy and Buildings, 2009, 41(8): 881-887.
  • 5Chen Y M, Lan L L. Fault detection, diagnosis and data recovery for a real building heating/cooling bill ing system[J]. Energy Conversion and Management, 2010, 51(5): 1015-1024.
  • 6肖赋,王盛卫,徐新华,葛高明.基于主成分分析法的空调系统传感器自动故障诊断[J].建筑科学,2008,24(6):34-39. 被引量:6
  • 7Wang S W, Xiao F. AHU sensor fault diagnosis u- sing principal component analysis method[J]. Energy and Buildings, 2004, 36(2) : 147-160.
  • 8Du Z M, Jin X Q, Wu L Z. PCA-FDA-based fault di- agnosis for sensors in VAV systems [J]. Hvac&R Research, 2007, 13(2): 349-367.
  • 9Wang S W, Chen Y M. Sensor validation and recon- struction for building central chilling systems based on principal component analysis[J]. Energy Conver- sion and Management, 2004, 45(5): 673-695.
  • 10徐新华,杨春生,王盛卫.基于小波变换的传感器故障诊断研究[J].建筑科学,2007,23(12):72-75. 被引量:3

二级参考文献77

共引文献81

同被引文献229

引证文献21

二级引证文献219

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部