高压断路器防跳回路的应用及问题探讨 被引量:52

Application and discussion of anti-bouncing circuit for high-voltage breaker
在线阅读 下载PDF
导出
摘要 针对电力工程中保护装置、断路器及操作箱型号多样、设计不统一,导致现场调试中断路器本体机构箱的防跳回路与保护装置操作箱的防跳回路无法配合、无法重合闸的问题,一般采用解除操作箱防跳回路的方法。对常见的操作箱和断路器本体防跳回路并联防跳和串联防跳"二选一"的设计原则讨论后,提出在同时保留操作箱和断路器本体防跳回路的情况下,采用合闸监视回路中串入断路器的常闭辅助触点的方法,确保防跳断路器不会经过合闸监视回路自保持,不会出现无法再次合闸或跳、合闸监视灯同时亮的现象。该方法已在实际中应用并证明防跳功能是正确、可靠的。 As the designs for various types of protective device,breaker and operating box are not standardized in power projects,the anti-bouncing circuit of circuit breaker operating mechanism and the anti-bouncing circuit of protective device operating box could not cooperate properly at the same time with the breaker in reclosing operation during site commissioning, which is generally solved by disabling the anti-bouncing circuit of operating box. The "one from two" principle is discussed and it is suggested to insert the normal-close contact of circuit breaker in the closing monitoring circuit while both the anti-bouncing circuits are kept,which ensures the proper cooperation. Practical application proves its reliability and correctness.
出处 《电力自动化设备》 EI CSCD 北大核心 2010年第10期106-109,共4页 Electric Power Automation Equipment
关键词 断路器 防跳回路 操作箱 重合闸 合闸监视 breaker anti-bouncing circuit operating box reclosing closing monitoring
  • 相关文献

参考文献10

二级参考文献8

  • 1..火力发电厂、变电所二次接线设计技术规程(Technical Code for Designing of Electrical Secondary Wiring in Fossil Fuel Power Plants and Substations)[S].国家经贸委(National Economic and Trade Committee),2001..
  • 2卓乐友 董柏林(ZHUO Le-you DONG Bo-lin).电力工程电气设计手册:第二册(Electrical Designing Manual for Electrical Engineering,Book Two)[M].北京:水利电力出版社(Beijing:Hydraulic and Electric Power Press),1991..
  • 3国家电力调度通讯中心(NationalPowerDispatchandCommunicationCenter).电力系统继电保护实用技术问答(Manual of Power System Protection Practical Technique)[M].北京:中国电力出版社,2000..
  • 4华北电力科学研究院(NorthChinaElectricPowerScienceInstitute).发电厂及电力系统反事故技术措施汇编(Corpus of Power Station and System Restraining Accident Document)[Z].北京:华北电力科学研究院(Beijing:North China Electric Power Science Institute),..
  • 5.华北电力调度局文件《印发"关于进口及引进技术生产的开关防跳回路的反事故措施"的通知》[Z].,..
  • 6电力工程电器设计手册第2册电气二次部分.
  • 7王轶成,刘波.断路器防跳回路的典型接线及其应用[J].电力系统自动化,2001,25(1):69-70. 被引量:41
  • 8林榕,曹树江.CSL 101与LFP-901线路保护重合闸应用问题的分析[J].电网技术,2003,27(10):78-81. 被引量:9

共引文献135

同被引文献176

引证文献52

二级引证文献90

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部