摘要 随着“西电东送”工程的开展以及紧凑型输电技术的应用,高海拔紧凑型线路在中国不断出现。为了保证这些线路带电作业能安全进行,需要对带电作业过程中的安全距离和组合间隙进行研究。笔者针对500kV高海拔紧凑型输电线路带电作业进行了一系列试验研究,对海拔为2000~3000m的紧凑型线路带电作业安全距离与组合间隙进行了危险率计算,计算结果表明,德宏高海拔紧凑性输电线路直线塔边相、中相和下相带电作业安全距离和组合间隙满足安全性要求,研究结果可为在500kV紧凑型高海拔输电线路杆塔设计与带电作业开展提供技术参考。 With the implement of 'power transmission from west to east' project and the application of compact transmission technology, many compact transmission lines have been applied in China , even in high altitude areas of China. In order to carry out living work on these lines , it is necessary to study the approach distance and complex gap during living work. A serial experiments have been carried out to reseaerch the living work of 500 kV compact transmission lines in high altitude area. The risk rate of approach distance and complex gap of living work on compact transmission line at altitude between 2 000 m and 3 000 m are calculated according test results. The results of calculation show that approach distance and complex gap of Dehong compact highaltitude 500 kV transmission line satisfy the safety requirement of living work. Research results provide references for the design of pole and tower and impeletion of living work of 500 kV compact transmission lines in high altitude area.
出处 《高压电器》 CAS CSCD 北大核心 2010年第4期35-39,共5页 High Voltage Apparatus
关键词 带电作业 安全距离 组合间隙 高海拔 紧凑型 live line work safe distance prtfolio clearance high altitude compact