摘要
2008年的冰灾对线路保护通道产生了严重影响,冰灾中线路保护均采用专用光纤通道对突发情况应变能力太差。通过对常规的几种继电保护通道方式的分析比较,对220kV线路保护通道配置原则进行了调整。以220kV方圆-岗阳线为例,根据新的配置原则对线路保护进行了通道配置,通过理论计算分析论证配置的合理性。对新的保护通道配置原则提出了一些看法。
The snow storm disaster in southern China occurred in early 2008 left a serious impact to the line relay protection channel adhering to the transmission line, due to the poor adaptability to sudden accidents of communication channel based on optical fiber, which is widely used in field of transmission line relay protection. Based on the comparison and analysis of several kinds of commonly used protection communication channels, the principle for 220 kV transmission line protection channel scheme is adjusted. Theoretic calculation is made to demonstrate the reasonability of the new principle application in 220 kV Fangyuan-Gangyang line and further suggestions on the new principle for 220 kV transmission line protection channel scheme are given.
出处
《电力系统保护与控制》
EI
CSCD
北大核心
2010年第7期94-97,101,共5页
Power System Protection and Control
关键词
继电保护
复用
传输延时
通道配置
protective relaying
multiplexing, transmission delay, channel scheme