期刊文献+

带并联电抗器输电线路永久性故障的时域判别方法 被引量:18

Time-domain method to identify permanent fault of transmission line with shunt reactor
在线阅读 下载PDF
导出
摘要 根据瞬时故障恢复电压阶段输电线路的状态建立参考模型,在时域中根据本端电气量求取并联电抗器故障相电流,并以计算电流与实测电流之差的模值作为动作量,以电抗器故障相实测电流的模值作为门槛值,进行永久性故障判别。发生瞬时故障,恢复电压阶段的线路状态与建立的模型吻合,电流计算值和实测值相同,动作量小于制动量;发生永久性故障,线路状态与建立的模型不吻合,电流计算值和实测值不同,动作量大于制动量。仿真验证表明,该方法能够准确地区分瞬时故障和永久性故障,能够用于自适应重合闸。 A reference model is established according to the states of transmission line during voltage restoration from temporary fault,based on which,the faulty phase current of local shunt reactor is calculated with local electrical variables in time-domain. With the difference between calculated and measured currents as the operating component and the measured current as the threshold,the criterion of permanent fault identification is founded. For a temporary fault,the calculated and measured currents are same because the state of transmission line accords with the established model,the operating component is smallerthan the threshold. For a permanent fault,because the current calculated by the transient model is far away from the measured current,the operating component is larger than the threshold. Simulation results show that the proposed criterion identifies the permanent fault correctly,which can be applied to the adaptive reclose.
出处 《电力自动化设备》 EI CSCD 北大核心 2009年第7期22-27,共6页 Electric Power Automation Equipment
基金 国家自然科学基金资助项目(50877062) 高等学校博士学科点专项科研基金资助项目(20060698014)~~
关键词 电力系统 输电线路 自适应重合闸 并联电抗器 时域 power system transmission line adaptive reclose shunt reactor time- domain
  • 相关文献

参考文献22

  • 1宋国兵,索南加乐,孙丹丹.输电线路永久性故障判别方法综述[J].电网技术,2006,30(18):75-80. 被引量:67
  • 2葛耀中.在单相自动重合闸过程中判别瞬时故障和永久性故障的方法.西安交通大学学报,1984,18(2):23-32.
  • 3GE Yaozhong,SUI Fengha,XIAO Yuan. Prediction methods for preventing single-phase re-closing on permanent fault[J].IEEE Trans on Power Delivery, 1989,4( 1 ) : 114-121.
  • 4AGGARWAL R K,JOHNS A T,SONG Y H,et al. Neural-network based adaptive autoreclosure technique for EHV transmission systems [ J ]. IEE Proceedings Generation, Transmission and Distribution, 1994,141 (2) : 155 - 160.
  • 5FITTON D S,DUNN R W,AGGARWAL R K,et al. Design and implementation of an adaptive single pole auto re-closure technique for transmission lines using artificial neural networks[J]. IEEE Trans on Power Delivery, 1996,11 (2) :748 - 756.
  • 6DJURIC M B,TERZIJA V V. A new approach to the arcing faults detection for fast auto reclosure in transmission systems [J]. IEEE Trans on Power Delivery, 1995,10(4) : 1793-1798.
  • 7TERZUA V V,RADOJEVIC Z M. Numerical algorithm for adaptive autoreclosure and protection of medium-voltage overhead lines[J]. IEEE Trans on Power Delivery,2004,19(2):554-559.
  • 8BO Z Q,AGGARWAL R K,JOHNS A T,et al. New concept in transmission line reclosure using high-frequency fault transients [J]. IEE Proceedings Generation,Transmission and Distribution, 1997,144(4) :351-356.
  • 9SANG-PIL A,CHUL-HWAN K,AGGARWAL R K,et al. An alternative approach to adaptive single pole autoreclosing in high voltage transmission systems based on variable dead time control[J]. IEEE Trans on Power Delivery,2001,16(4):676-686.
  • 10范越,施围.输电线路单相自动重合闸中电压判据的修正[J].电力系统自动化,2000,24(6):44-47. 被引量:56