期刊文献+

输电线路单相自动重合闸中电压判据的修正 被引量:56

MODIFICATION OF VOLTAGE CRITERION IN THE SINGLE-POLE AUTOMATIC RECLOSING OF TRANSMISSION LINES
在线阅读 下载PDF
导出
摘要 分析了区分输电线路瞬时性与永久性故障的电压判据、补偿电压判据及组合补偿判据成立的条件,指出其存在的缺陷,提出了修正电压判据。该判据区分瞬时性和永久性故障正确率高,且有简单、易行的特点,不仅适用于短线,而且适用于重负荷长线和带并联电抗器的线路。已有的试验数据表明,该判据是有效的。 The conditions of the voltage criterion, voltage compensation criterion and combined voltage compensation criterion for identifying 'transient' and 'permanent' faults are analyzed. It is pointed out that sometimes the fault can't be identified by the three criteria or the identification result is wrong. Based on the analysis, the modified voltage criterion is proposed. It can idenify the 'transient' and 'permanent' faults more correctly and is simple and easy. It can be used not only in the short transmission lines but also in the long transmission lines with heavy load or transmission lines with shunt reactors. The existing experimental data show that the modified voltage criterion is effective.
作者 范越 施围
机构地区 西安交通大学
出处 《电力系统自动化》 EI CSCD 北大核心 2000年第6期44-47,共4页 Automation of Electric Power Systems
关键词 单相接地 故障 输电线路 自动重合闸 电压判据 single-phase to ground fault permanent fault transient fault
  • 相关文献

参考文献2

二级参考文献2

  • 1Ge Yaozhong,IEEE Trans Power Delivery,1989年,4卷,1期
  • 2匿名著者,WXH-25型微机线路保护装置

共引文献58

同被引文献364

引证文献56

二级引证文献405