期刊文献+

基于双端不同步数据的故障定位算法 被引量:2

Fault location algorithms based on two-terminal unsynchronized data
原文传递
导出
摘要 基于故障时沿线电压的分布规律提出了两种实用性较强的故障测距算法,利用线路两侧的电压和电流正弦相量计算故障距离,不要求双端数据的同步,能消除过渡电阻的影响,具有较高的工程实用价值。着重对输电线路故障测距方法进行可行性验证,采用ATP仿真获得故障线路的电气量值,并用M atlab计算故障点位置,仿真结果表明该方法有较高的精度,能满足现场实际要求。 Two practical fault location algorithms were proposed based on the voltage distribution features along the transmission line during faults. The fault location was calculated using the current and voltage sinusoidal phasors at both ends without data synchronization, and the influence of the fault resistance can be eliminated. Verification of the methods' feasibility was emphasized. The electrical parameters of the fault line were acquired by ATP simulation, and the fault location was calculated with Matlab programming. Simulation results showed that the methods proposed could precisely locate the fault site and completely satisfied the field need.
出处 《华东电力》 北大核心 2009年第1期116-119,共4页 East China Electric Power
基金 自治区高校高技术研究重点项目(XJEDU2004I04) 自治区高技术研究发展计划项目(200614118)
关键词 输电线路 故障定位 双端不同步 ATP transmission line fault location two-terminal unsynchronized data ATP
  • 相关文献

参考文献14

二级参考文献124

共引文献290

同被引文献17

引证文献2

二级引证文献3

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部