一起油浸式电流互感器轻微冒顶异常试验解体分析 被引量:1

Analysis of a Slight Roof Fall Abnormality of Oil-Immersed Current Transformer Through Test and Disassembly
在线阅读 下载PDF
导出
摘要 文章介绍了一起110 kV油浸式电流互感器轻微冒顶异常的处理过程。通过油色谱和介损试验分析发现电流互感器内部出现了故障,然后经停电后予以解体检查,发现其内部一次绕组绝缘纸局部老化并伴有局部发热放电和包扎工艺缺陷,最后总结了该设备在后续运维过程中应注意的事项,以期为此类设备的运维和异常处理提供参考和借鉴。 This paper introduces the treatment of a slight abnormal roof fall of a 110 kV oil-immersed current transformer.Through the analysis of oil chromatography and dielectric loss test,a fault was found inside the current transformer.Then,after a power cut,it was disassembled and inspected,and it was found that the inner insulation paper of the primary winding was partly aged and accompanied by local thermal discharge and wrapping process defects.Finally,the paper summarizes the matters that should be paid attention to in the subsequent operation and maintenance of the equipment,in order to provide reference and guidance for the operation,maintenance and abnormality handling of this type of equipment.
作者 张宏 郭建 ZHANG Hong;GUO Jian(State Grid Jibei Electric Power Co.,Ltd.Qinhuangdao Power Supply Company,Qinhuangdao 066000,China)
出处 《安徽电气工程职业技术学院学报》 2025年第1期35-39,共5页 Journal of Anhui Electrical Engineering Professional Technique College
关键词 油浸式电流互感器 冒顶 油色谱 介损 解体分析 oil-immersed current transformer roof fall oil chromatography dielectric loss disassembly analysis