摘要
储能电站性能测试是确保储能电站稳定安全运行的关键环节。在简要介绍储能有功功率控制能力、无功功率控制能力、充放电转换时间、额定能量以及功率因数调节能力等检测方法基础上,针对某新能源场站无功功率控制能力测试和功率因数调节能力测试中发现的问题,分析了产生的原因,提出了改进的建议。
Performance test of energy storage power stations is a crucial step to ensure their stable and safe operation.The testing methods of several performance parameters are introduced,including the active power control capability,reactive power control capability,charge and discharge conversion time,rated energy,and power factor adjustment capability.Then,the problems found in the reactive power control capability test and the power factor adjustment capability test of a new energy station are discussed.Possible causes are analyzed and improvement measures are proposed.
作者
赵小阳
盛文杰
陶聪
何卓林
ZHAO Xiaoyang;SHENG Wenjie;TAO Cong;HE Zhuolin(Shenzhen Zhihe Smart Energy Co.,Ltd.,Zhengzhou 450000,China;Rundian Energy Science&Technology Co.,Ltd.,Zhengzhou 450000,China)
出处
《水电与新能源》
2025年第2期91-94,共4页
Hydropower and New Energy
关键词
储能电站
有功控制
无功控制
充放电
功率因数
energy storage power station
active power control
reactive power control
charging and discharging
power factor