期刊文献+

氨立式冷凝器强化传热管的研究与应用 被引量:1

Research and application of enhanced heat transfer tube in vertical ammonia condenser
在线阅读 下载PDF
导出
摘要 为提高氨立式冷凝器的传热性能 ,采用螺旋槽钢管为强化传热元件 ,与光滑钢管进行了对比试验 ,结果表明螺旋槽钢管的传热系数比光滑钢管高 1 2 .9%~ 65 .5 %。某冷冻厂的氨立式冷凝器应用螺旋槽钢管 ,经过一年多的运行测试 ,传热系数比用光滑钢管高 32 .6%~5 7%。 In order to improve heat transfer performance of vertical ammonia condenser,adopts spiral corrugated steel tube as the enhanced heat transfer element. The compared experiment with smooth steel tube shows that heat transfer of spiral corrugated steel tube is 12.9 %~65.5% higher than that of smooth steel tube. The spiral corrugated steel tube is applied in the vertical ammonia condenser of a factory, and the coefficient increase by 32.6%~57% over that of smooth steel tube.
机构地区 天津商学院
出处 《暖通空调》 北大核心 2002年第6期47-49,共3页 Heating Ventilating & Air Conditioning
关键词 传热管 氨立式冷凝器 螺旋槽钢管 强化传热 vertical ammonia condenser, spiral corrugated steel tube, enhanced heat transfer
  • 相关文献

参考文献3

二级参考文献5

  • 1罗国钦,高等学校化学学报,1989年,2期
  • 2曹一丁,工程热物理学报,1986年,7卷,1期
  • 3团体著者,换热器.上,1986年
  • 4汤--孙,沸腾传热和两相流动,1980年
  • 5陆应生,庄礼贤,陈广怀,陈慕玲,李若兰,魏福荣,苏德明,王振翔.横纹管氨卧式冷凝器传热强化的试验研究[J].制冷,1992(2):8-13. 被引量:6