期刊文献+

一起220 kV线路断路器单相误动作的事件分析 被引量:2

Event Analysis of Single-Phase Maloperation of 220 kV Line-Breaker
在线阅读 下载PDF
导出
摘要 针对某次220kV线路断路器检修时,出现的单相断路器先自动合闸又自动跳闸的异常情况,分析其原因为重合闸装置与分相配置“远方/就地”把手的断路器配合不当造成。梳理了典型线路保护设置“控回断线闭锁重合闸”的情况,并针对事件中三相不一致遥信因继电器动作持续时间小于测控装置防抖时间而无法上送的问题,提出了增加自保持回路和复归按钮的整改建议。 Aiming at the maloperation event that a single-phase circuit breaker of 220 kV line-breaker firstly automatically closed and then tripped during certain 220 kV line-breaker overhaul,this paper concluded the reason that the reclosing device matched improperly with the circuit breaker which configured with the phase-separated“remote/local”handle and combed the conditions of typical line-protection setting,the“control circuit disconnection blocking reclosing”.In terms of the problem that the three-phase inconsistent remote signal in the event couldn’t be sent because the relay action duration was less than the anti-shake time of the measurement and control device,this paper proposed the rectification suggestion of adding the self-holding circuit and the reset button.
作者 张翔 陈继拓 林帆 潘中达 ZHANG Xiang;CHEN Ji-tuo;LIN Fan;PAN Zhong-da(State Grid Wenzhou Electric Power Supply Company,Wenzhou 325000,China)
出处 《电工电气》 2019年第6期24-27,共4页 Electrotechnics Electric
关键词 三相不一致 重合闸 电力系统 控回断线 防抖时间 three-phase inconsistent reclosure power system control circuit disconnection anti-shake time
  • 相关文献

参考文献10

二级参考文献71

共引文献114

同被引文献12

引证文献2

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部