期刊文献+

地铁运营初期区间隧道气温变化规律研究 被引量:6

Research on Air Temperature of Metro Tunnel during the Initial Stage
在线阅读 下载PDF
导出
摘要 对苏州地铁2号线3个连续区间的隧道气温进行测试,分析隧道气温在夏季最热月和冬季最冷月的特征及动态变化规律。结果表明夏季隧道气温比冬季隧道气温高,夏季和冬季隧道气温分别在23.5~27.5℃和16.5~20℃之间变化;当室外气温达到30℃以上时,隧道风机对隧道气温有提升作用,车辆运营和停运时分别可提升约1.5℃和2℃。车辆运行时,冬季和夏季隧道气温均以行车间隔为周期呈锯齿形变化,冬季可能出现倒锯齿形变化;车辆运行与停运时隧道气温比较,夏季车辆运行时高,冬季车辆运行时低;夏季区间隧道中部气温与隧道长度呈正相关关系,冬季时隧道中部气温与隧道长度无规律性关系。 This paper aims to explore the air temperature characteristics and the change rules of several tunnels for the hottest month of summer and the coldest month of winter.The air temperature of three tunnels of the Suzhou Metro Line 2 was tested.The results show that the air temperature of the tunnel was higher in summer than it was in winter.The summer and winter air temperatures ranged from 23.5℃ to 27.5℃,and 16.5℃ to 20℃,respectively.When the outdoor temperature was above 30℃,the tunnel fan was able to improve the air temperature of the tunnel by 1.5℃ and 2℃ during,respectively,vehicle operation and vehicle outage.In both winter and summer,when the vehicle was running,the tunnel air temperature changed periodically,and the change period was the same as the departure interval.When the vehicle was running,the temperature was higher in summer and lower in winter,relative to the temperatures attained during vehicle outage.In summer,the air temperature at the middle interval of the tunnel was positively related to the length of the tunnel.In winter,the temperature at the interval showed no clear relationship with the length of the tunnel.
作者 姜波 JIANG Bo(JSTI Group, Nanjing 210003)
出处 《都市快轨交通》 北大核心 2018年第2期113-118,共6页 Urban Rapid Rail Transit
基金 苏州市轨道交通集团有限公司科研项目(SZZG06Y J1030014)
关键词 地铁 区间隧道 隧道气温 测试 变化规律 metro metro tunnel air temperature of tunnel test variation rule
  • 相关文献

参考文献10

二级参考文献60

共引文献127

同被引文献37

引证文献6

二级引证文献8

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部