摘要
为实现高地温隧道施工环境的有效控制,文章采用ANSYS Fluent软件建立三维数值模型,系统研究了不同通风风速(0.5~3.0m/s)对隧道内部温度分布的影响规律。研究表明,风速2.0m/s时可达到最优运行效果,温度降幅10.8℃,系统功率62.4kW,温度场标准差1.6℃。该研究可为高地温隧道通风系统设计和运行优化提供参考。
In order to realize the effective control of the construction environment of the tunnel with high ground temperature,this paper uses ANSYS Fluent software to establish a three-dimensional numerical model,and systematically studies the infuence law of 0.5一3.0m/s different ventilation wind speed on the internal temperature distribution of the tunnel.The study shows that the optimal operation effect can be achieved when the wind speed is 2.0m/s,and the temperature reduction is 10.8℃,the system power is 62.4kW,and the standard deviation of the temperature ficld is 1.6℃.This study can provide a reference for the design and operation optimization of high geothermal tunnel ventilation system.
作者
王明山
WANG Mingshan(Beijing Zhongxi Huake Traffic Construction Technology Co.,Ltd.,Beijing 100195,China)
关键词
通风风速
高地温隧道
温度分布
数值模拟
ventilation and wind speed
high ground temperature tunnel
temperature distribution
numerical simulation