期刊文献+

空调器用翅片管式蒸发器铜管点蚀分析及预防措施 被引量:6

Analysis and preventive measures on pitting corrosion in finned-tube evaporator's copper tubes of air conditioner
在线阅读 下载PDF
导出
摘要 针对空调器用翅片管式蒸发器铜管点蚀泄漏故障,结合铜管点蚀失效机制,从使用环境及蒸发器结构方面进行分析。研究发现,空气中含有的氯气或氯化物、氨气等溶解于冷凝水中形成腐蚀性离子,蒸发器相邻翅片叠加位置存在明显的孔洞状间隙,使冷凝水长期积存引起腐蚀性离子对铜管表面的腐蚀破坏作用,是导致蒸发器铜管点蚀泄漏的根本原因,鉴于此,提出避开腐蚀源、采用高耐腐蚀铜管、在铜管表面涂覆缓蚀剂、优化蒸发器翅片与铜管接触结构等预防措施。 Leakage caused by pitting corrosion in finned-tube evaporator's copper tubes of air conditioner is studied in the aspects of operational environment and evaporator's structure, as well as the copper tube pitting failure mechanism. It is found that the chlo rine (chloride) and ammonia contained in the air can be dissolved in the condensate water, which turn to corrosive ions. Obvious hole-shaped gaps existing in the stacking adjacent position of evaporator's fins, allow condensate water to accumulate and bring corrosive i- ons, which damage the copper tube's surface and cause pitting corrosion leakage. Based on it, some prevention measures are proposed, such as avoiding corrosion source, using high anti corrosion copper tubes, coating corrosion inhibitor on the copper surface, opti- mizing the contacting structure of evaporator and copper tube, etc.
出处 《制冷与空调》 2014年第2期74-77,共4页 Refrigeration and Air-Conditioning
关键词 空调器 翅片管式蒸发器 铜管 点蚀 air conditioner finned-tube evaporator copper tube pitting corrosion
  • 相关文献

参考文献6

二级参考文献45

  • 1马植桢,刘家骅.工厂环境对循环水水质的影响[J].工业水处理,1994,14(3):31-32. 被引量:1
  • 2-.化学工程手册[M].化学工业出版社,1989(5).21-250,376,373.
  • 3窦照英.电力工业的腐蚀与防护[M].北京:化学工业出版社,1995..
  • 4吴荫顺.腐蚀试验方法与防腐蚀检测技术[M].北京:化学工业出版社,1996..
  • 5西安热工研究所.热工技术手册(电厂化学)[M].北京:水利电力出版社,1993..
  • 6龚洵洁.热力设备的腐蚀与防腐[M].北京:中国电力出版社,1998..
  • 7西安热工所情报室(译).-[J].热力发电,1973,(7):1-43.
  • 8沈祖灿(译).热能动力设备金属的腐蚀与防护[M].北京:水利电力出版社,1988..
  • 9沈祖灿(译).火力发电厂大容量机组水化学工况[M].北京:电力工业出版社,1982..
  • 10佚名.火力发电厂水、汽试验方法[M].北京:水利电力出版社,1984..