期刊文献+

空冷电厂一起变压器平衡绕组故障的分析及处理 被引量:2

Analysis on transformer balance winding fault of an air-cooled power plant and treatment
在线阅读 下载PDF
导出
摘要 介绍了变压器平衡绕组的作用,分析了一起比较少见的Yyn0+d连接组别的空冷电厂变压器平衡绕组短路引起差动保护动作的案例。对于变压器两侧电流转化计算,采用了一种快捷的计算方法,可准确判断故障所在位置,为故障处理奠定了基础。 The function of transformer balance winding was introduced.An infrequent short circuit fault of transformer balance winding was introduced.The transformer is installed in an air-cooled power plant and connected in mode of Yyn0+d,and the short circuit fault of its balance winding had caused the differential protection to trip.A new fast method was adopted for transformation and calculation of first and second currents of the transformer.The fault position can be determined correctly by the new method,which provides a base for the fault treatment.
机构地区 华能铜川电厂
出处 《华电技术》 CAS 2013年第7期53-55,78,共3页 HUADIAN TECHNOLOGY
关键词 变压器 平衡绕组 差动保护 短路简化分析 transformer balance winding differential protection simplified analysis on short circuit fault
  • 相关文献

参考文献2

二级参考文献1

  • 1王正官,王述伦,陈昌顺.变压器试验[M].北京:机械工业出版社,1998.

共引文献23

同被引文献29

引证文献2

二级引证文献12