摘要
计算了带有平衡绕组的轴向分裂变压器发生短路故障时,短路电流及并联绕组电流的分配;分析了平衡绕组结构的改进措施,并对结构改进前后各绕组受力进行了计算比较。结果表明,结构改进后,当低压绕组发生突发短路故障时,短路绕组所受到的电磁力降低了。
The low voltage winding of a three phase axial split winding type transformer was damaged by a sudden short circuit fault. The current of each winding and current distribution in HVI and HVZ are calculated. TO increase the ability to withstand a sudden short^circuit trouble, the tertiary winding of the transformer is redesigned. The magnetic flux diStrbution and short-circuit force and strength of the transformer are calculated by FEM. The calculation results show that the new design of the tertiary winding reduces the shoyt-circuit force.
出处
《华北电力大学学报(自然科学版)》
CAS
北大核心
2000年第1期29-32,共4页
Journal of North China Electric Power University:Natural Science Edition
关键词
分裂变压器
平衡绕组
有限元
结构分析
: split transformer: tertiary winding: magnetic field
magnetic force: FEM