基于可控短路技术的系统阻抗测量方法在孤岛检测中的应用 被引量:7

A Novel Method of Impedance Measurement Used in Islanding Detection Based on Controllable Short-circuit Technology
在线阅读 下载PDF
导出
摘要 迅速有效的孤岛检测技术对于分布式发电系统的安全可靠有着十分重要的意义。针对分布式发电系统的孤岛检测问题,提出了一种简单有效的检测方法:在分布式电源出口端任意两相间设置一个晶闸管,通过控制晶闸管周期性瞬时导通,人为造成分布式电源出口端周期性瞬时相间短路,从而产生周期性短路脉冲电压和电流。基于该短路脉冲电压和电流,实时获得分布式电源出口处的系统阻抗,通过监测该系统阻抗的变化即可迅速判断出分布式电源是否处于孤岛状态。文中也对检测信号间的干扰进行了有效分析。理论推导、仿真和模拟实验都验证了该方法的有效性。 It is very important for a distributed generating system to have an effective islanding detection component.A new and effective islanding detection scheme is proposed.The scheme includes a thyristor placed between any two phases just by the port of a distributed generator(DG).An artificial short time phase-to-phase short circuit is formed by triggering the thyristor periodically,so the short-circuit current and voltage pulse can be extracted.Because of this,the frequency response of system can be acquired according to the theory of harmonic impedance,so that the impedance measured from DG port can be obtained. Whether the DG is islanding can be determined quickly by monitoring the changes of this impedance.At the same time, disturbances between different DG's detecting signals are analyzed.This method is proved to be correct and effective by theoretical analysis,simulation and mockup experiment.
出处 《电力系统自动化》 EI CSCD 北大核心 2013年第2期119-124,共6页 Automation of Electric Power Systems
基金 山东省自然科学基金资助项目(Z2008F10)~~
关键词 分布式电源 孤岛检测 晶闸管 谐波阻抗 distributed generator(DG) islanding detection thyristor harmonic impedance
  • 相关文献

参考文献11

  • 1雷亚洲.与风电并网相关的研究课题[J].电力系统自动化,2003,27(8):84-89. 被引量:460
  • 2丁磊,潘贞存,王宾.分散电源并网对供电可靠性的影响分析[J].电力系统自动化,2007,31(20):89-93. 被引量:24
  • 3XU W, ZHANG G, LI C, et al. A power line signaling based technique for anti-islanding protection of distributed generators Part Ⅰ scheme and analysis[J]. IEEE Trans on Power Delivery, 2007, 22(3): 1758-1766.
  • 4WANG W, KLIBER J, ZHANG G, et al. A power line signaling based technique for anti-islanding protection of distributed generators Part Ⅱ field test results[J]. IEEE Trans on Power Delivery, 2007, 22(3) : 1767-1772.
  • 5ANSI/IEEE Std 1001--1988 IEEE guide for interfacing dispersed storage and generation facilities with electric utility systems[S]. 1988.
  • 6KIM J E, HWANG J S. Islanding detection method of distributed generation units connected to power distribution system[C]// Proceedings of 2000 International Conference on Power System Technology (PowerCon 2000), December 4-7, 2000, Perth, Australia: 643-647.
  • 7张纯江,郭忠南,孟慧英,刘炜.主动电流扰动法在并网发电系统孤岛检测中的应用[J].电工技术学报,2007,22(7):176-180. 被引量:61
  • 8任碧莹,钟彦儒,孙向东,同向前.基于周期交替电流扰动的孤岛检测方法[J].电力系统自动化,2008,32(19):81-84. 被引量:23
  • 9马静,米超,王增平.基于谐波畸变率正反馈的孤岛检测新方法[J].电力系统自动化,2012,36(1):47-50. 被引量:33
  • 10KLIBER J, WANG W, XU W. Local anti-islanding protection for distributed generators based on impedance measurements [C]// Proceedings of 2008 IEEE Canada Electric Power Conference (EPEC 2008), October 6-7, 2008, Vancouver, Canada: 1-5.

二级参考文献87

共引文献581

同被引文献95

引证文献7

二级引证文献61

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部