期刊文献+

换流站支柱绝缘子在高海拔地区的污秽外绝缘特性 被引量:15

Pollution Flashover Performance of Converter Station Post Insulators at High Altitude Area
原文传递
导出
摘要 支柱绝缘子作为换流站必不可少的绝缘配件,研究其外绝缘性能有重要意义。为此,总结了国内外关于换流站支柱绝缘子的污秽外绝缘特性研究工作,并结合我国特高压直流输电工程面临的特有技术问题,在实际高海拔地区对特高压直流全尺寸支柱绝缘子试品进行了人工污秽试验研究。试验分别得到了瓷和复合2种材质的换流站支柱绝缘子在不同污秽度条件下的50%污耐受电压曲线,并与相同污秽度条件下的污雨闪电压进行了对比,最后将该试验结果与不同单位的研究成果进行了比较。研究表明:直径及伞形结构对支柱瓷绝缘子的污闪特性有明显影响;支柱绝缘子的污闪电压与串长近似呈线性关系;支柱绝缘子的污雨闪电压高于其相同污秽条件下的污闪电压,因此支柱绝缘子的外绝缘设计应以污闪电压为主。 In this paper,the previous research work of the polluted outdoor insulating performance of converter stations post insulators is summarized.Moreover,according to the peculiar technology problems of UHV DC projects' external insulation in China,such as high altitude and heavy pollution etc.,the pollution flashover performances of full-size ±800 kV post insulators made of both porcelain and composite for UHVDC converter stations are reported and investigated by artificial contamination tests at actual high altitude area.Furthermore,the pollution flashover voltages of post insulators in fog and under rain in the same pollution level conditions are compared.Meanwhile,discussion and comparison are presented for the research results of previous work and this paper.The results of artificial contamination tests show that the rod diameter and the shed configuration has a significant influence on pollution flashover performance of post insulator;the relationship between the pollution flashover voltage and the insulation distance is approximately linear at actual high altitude area for post insulators;the outdoor insulation design of post insulators should give priority to the pollution flashover voltages in fog,since the voltages are lower in rain.
出处 《高电压技术》 EI CAS CSCD 北大核心 2012年第10期2568-2574,共7页 High Voltage Engineering
基金 国家重点基础研究发展计划(973计划)(2009CB724503)~~
关键词 支柱绝缘子 污闪特性 高海拔地区 特高压直流 全尺寸试品 外绝缘 人工污秽试验 post insulator pollution flashover performance high altitude area UHVDC full-size insulator external insulation artificial contamination test
  • 相关文献

参考文献31

  • 1Baker A C, Zaffanella L E, Anaivino L D, et al. Contamination performance of HVDC station post insulators[J]. IEEE Trans- actions on Power Delivery, 1988, 3(4): 1968-1957.
  • 2Baker A C, Zaffanella L E, Anaivino L D, et al. A comparison of HVAC and HVDC contamination performance of st:ition post insulators[J]. IEEE Transactions on Power Delivery, 1989, 4 (2) : 1486-1491.
  • 3Naito K, Kunieda S, Hasegawa Y, et al. DC contamination per formance of station insulator[J]. IEEE Transactions on Electri- cal Insulation, 1988, 23(6) : 1015-1023.
  • 4Sundararajan R, Gorur R. Pollution performance of DC station post insulator using a dynamic model[C]//Annual Report Con- ference on Electrical Insulation and Dielectric Phenomena. Poco- no Manor, USA: IEEE, 1993: 592-597.
  • 5Seta T, Nagai K, Naito K, et al. Studies on performance of contaminated insulators energized with DC voltages[J]. IEEE Transactions on Power Apparatus and Systems, 1981, 100(2), 518-527.
  • 6Naito K, Matsuoka R, Ito S, et al. An investigation of the hori- zontally mounted insulators for HVDC stations[J] IEEE Trans- actions on Power Delivery, 1989, 4(1): 653-666.
  • 7Fazelian M, Wu C Y, Cheng T C, et al. A Study of the Profile of HVDC insulators[J]. IEEE Transactions on Electrical Insu- lation, 1989, 24(1): 119-125.
  • 8Wu D, Astrom U, Almgren B, et al. Investigation into alterna- tive solutions for HVDC station post insulators[C]//Proceed- ings of International Conference on Power System Technology. Beijing, China: IEEE, 1998: 512-515.
  • 9Wu D, Hartings R. Astrom U. The performance of station post insulator in uneven rain under DC voltage[C]//Proceedings of 9th International Symposium on High Voltage Engineering. Graz, Austria: Is. n.], 1995: 3237.