测控装置通信频繁中断故障原因分析及处理 被引量:5

Analysis and Treatment of Frequent Communication Interruption of Measurement and Control Equipment
在线阅读 下载PDF
导出
摘要 针对一500 kV变电站长期出现的站内测控装置不定期报通信中断和五防校验超时信号,导致操作失败的现象,通过截取报文分析,发现由于存在大量的UDP心跳报文和联锁报文,造成广播网络风暴引起通信中断,通过对网络层交换机划分VLAN,隔离广播流量,成功解决了该问题。 The operation failure problem caused by random communication interruption of measurement and control equipment and the overtime of misoperation logic verification in a 500kV substation is analyzed by intercepting messages. It is founded that the interruption is caused by broadcast storm which is caused by a large amount of UDP messages and interlocking messages. The problem is solved by dividing VLAN of switch to isolate broadcast traffic.
作者 刘滨涛 黄倩
出处 《广西电力》 2012年第3期18-19,40,共3页 Guangxi Electric Power
关键词 测控装置 通信中断 广播报文 虚拟网段 communication interruption, measurement and control equipment, broadcast message, virtual network