期刊文献+

启动循环泵溢流管泄漏原因分析 被引量:1

Reasons Analysis on Leakage of Overflow Tube of Starting Circulating Pump
在线阅读 下载PDF
导出
摘要 通过宏观分析、金相检验、扫描电镜及X射线能谱分析、维氏硬度试验等方法,对某电厂启动循环泵溢流管的泄露原因进行了分析。结果表明:该溢流管失效的性质是氯离子导致的不锈钢应力腐蚀开裂;溢流管失效是材料、应力和介质三方面问题联合作用的结果,主要原因是氯化物在溢流管异种钢焊接接头外表面附着和富集。 The leakage reasons of the overflow tube of a starting circulating pump were studied by means of macroscopic analysis,metallographic examination,scanning electron microscope(SEM) analysis and energy dispersive spectrometer(EDS) analysis and hardness test.The results show that the failure property of the overflow tube was stress corrosion cracking caused by chloridion,and the failure was the interaction results of material quality,stress and medium.The main reason for the failure was the adhesion and enrichment of chlorides on the overflow tube dissimilar steel welding joint outer surface.
出处 《理化检验(物理分册)》 CAS 2012年第4期261-265,共5页 Physical Testing and Chemical Analysis(Part A:Physical Testing)
关键词 启动循环泵 溢流管 泄露 应力腐蚀开裂 starting circulating pump overflow tube leakage stress corrosion cracking
  • 相关文献

参考文献2

二级参考文献4

  • 1Wang Zhengqiao, Wu oulin, Ji Xiaochun. Study on The Stress Corrosion Cracking Process of Austemitic Stainless Steel in Boiling 42% MgCI, Solution. 4th Asian-Pacific Corrosion Control Conference, Tokyo, JAPAN,1985.26-31.
  • 2纪晓春 吴幼林 邹显智 王正樵.核工程材料的应力腐蚀破裂及喷丸表面改性研究[A]..轻水堆腐蚀研讨会[C].深圳:中国腐蚀与防护学会能源工程专业委员会,1993.1-20.
  • 3R. Katsura, M. Kodama, S. Nishimura, DL-EPR Study of Neutron Irradiation In Type 304 Stainless Steel[J]. Corrosion, 1992,48(5):384-390.
  • 4A. J. Jaeobs, G. P. Waozadio, S. a. Wilson, Stress Corrosion, Testing of Irradiated Type 304SS Under Constant Load [J]. Corrosion, 1993,49(2):145-155.