10kV架空绝缘导线雷击断线原因机理分析及防护措施 被引量:43

Mechanism Analysis and Protective Measures on the Lightning Break Reason of 10 kV Overhead Insulation Conductor
原文传递
导出
摘要 10 kV配电网架空绝缘导线经常发生雷击断线事故,严重影响配电线路的供电可靠性。笔者结合海南地区某10 kV配电线路的具体实际情况,通过现场调研及大量的理论分析计算,对架空绝缘导线雷击断线事故的原因和机理进行了深入剖析,并提出了提高线路绝缘水平和安装引弧跳线等预防架空绝缘导线雷击断线的措施,现场运行表明,这些措施对预防绝缘导线断线事故的发生效果十分显著。 The lightning break accident often happened on 10 kV distribution grid overhead line insulation conductor,which seriously influence the power supply reliability of distribution lines.Through field investigation and a large number of theory analysis and calculation,the author analyses the reason and mechanism about aerial insulation wire lightning break accident,combined with the specific circumstances of a 10 kV power circuit in Hainan,and the measures for preventing the overhead insulation conductor from lightning break,such as improving line insulation level,installation of arc starting jump line and so on.The Field operation shows that the effect of these measures is notable for preventing insulation conductor break accident.
出处 《电瓷避雷器》 CAS 北大核心 2012年第1期65-69,共5页 Insulators and Surge Arresters
关键词 10kV架空绝缘导线 雷击断线 宏观原因 断线机理 防雷措施 10 kV overhead insulation conductor lightning break macroscopic reason break mechanism lightning protection measures