摘要 列举了变电站10kV母线短路故障几率较高的原因,论述了10kV母线短路电流对开关柜和主变的危害,提出了缩短10kV母线短路故障切除时间的必要性和三种措施。一是缩短主变保护切除10kV侧开关的时间,二是装设简易母差保护,三是装设电弧光保护。比较了三种措施的优缺点,以及各自的适用范围。介绍了东莞供电局的应用情况。 This paper enumerates the most possible causes of short-circuit faults on lOkV bus in transformer substation, discusses the hazards of the short-circuit current on lOkV bus to switch cabinet and main transformer, the necessity and three methods to shorten the clearing time of fault are put forward. It includes shortening the clearing time of the transformer protection,equipping simple bus differential protection,and equipping arc protection. The disadvantage and shortcomings of these three methods and their applicability are compared, and the application in Dongguan Power Supply Bureau is introduced.