摘要
基于湖南电网2015年规划数据,应用电力系统分析综合程序(power system analysis software package,PSASP)分析了±800 kV酒泉特高压直流入湘对湖南电网暂态电压稳定性的影响。分析结果表明:±800 kV酒泉直流入湘后湖南电网机组的开机数量和电容器组投切量均将相应减少,但湘东500 kV环网的无功损耗将增加,同时扰动后酒泉直流还将从湘东500 kV环网吸入大量无功,最终减弱了扰动后湖南电网电压的恢复能力,降低了湖南电网的暂态电压稳定水平。分析结果可为其他电网研究特高压直流对受端电网的影响提供参考。
According to the planned data of Hunan power grid for the year of 2015, the influence of transmitting power via ±800 kV HVDC transmission line from Jiuquan to Hunan power grid on transient voltage stability of Hunan power grid is simulated by power system analysis software package (PSASP) Simulation results show that under the power transmission from Jiuquan to Hunan via ±800 kV HVDC transmission line the number of being operated generating units in Hunan power grid as well as the capacity of switched over capacitor banks are reduced correspondingly, however the reactive power loss of 500 kV electromagnetic looped network in East Hunan will increase, and after the disturbance the ±800 kV HVDC system will absorb large amount of reactive power from 500 kV electromagnetic looped network in East Hunan, thus the ability of voltage recovery of Hunan power grid after the disturbance will be weakened and the transient voltage stability level of Hunan power grid will be decreased.
出处
《电网技术》
EI
CSCD
北大核心
2012年第2期23-28,共6页
Power System Technology
关键词
±800
KV
特高压直流
暂态电压
稳定
湖南
电网
±800 kV
ultra high voltage direct current (UHVDC)
transient voltage
stability
Hunan power grid