摘要
对电容型设备的带电测试结果能真实地反映设备在运行中的绝缘状况,能及时发现设备的绝缘缺陷,并且可减少停电时间,提高设备可用率。本文利用TIR2000绝缘参数测试仪,通过对绝缘良好设备的长期带电测试结果和绝缘缺陷设备的现场带电测试结果进行分析比较,相对比较法带电测试技术所获得的测试数据相对稳定,是行之有效的测试方法,可部分取代常规预防性试验。
The on-line measurement result can reflect Insulation condition of the capacitive equipments,find the Insulation defects timely,and increasing equipment operation rate.Based on TIR2000 measuring instrument for insulation parameter,this paper analysis the on-line measurement results of equipment of good insulation and equipment of Insulation defects,the measurement data with Relative Comparison Method can capture real insulation data of capacitive equipment.
出处
《电测与仪表》
北大核心
2010年第12期24-26,30,共4页
Electrical Measurement & Instrumentation