期刊文献+

冬季极端天气状况下空气源热泵运行实验研究 被引量:12

EXPERIMENTAL STUDIES ON THE OPERATION OF AIR SOURCE HEAT PUMP IN EXTREME WINTER WEATHER
原文传递
导出
摘要 对夏热冬冷地区某住宅的空气源热泵空调器在降雪天气状况下的运行性能进行了实测研究。结果表明:制热量平均值较额定值下降约15%,瞬时值最大下降约30%;制热工况平均COP值为2.66,较额定值下降11.3%,包含除霜在内的运行周期平均COP值为2.37,较额定值下降20.9%,除霜耗电量为总耗电量的9.2%;不受结霜影响的瞬时制热量最大值达到额定值的94%~98%;室内机风速变化引起的制热量变化幅度约为4%。分析表明,室外机在结霜状况下工作是导致制热量及COP值下降的主要原因,先进的除霜方式是降低结霜对制热量的影响与提高运行能效的关键。 The operating performance of air source heat pump on snowy days for a residence in hot summer and cold winter areas was tested; the results show that when comparing to the rated heating capacity, the average of heating capacity falls 15 % and the droop rate of the maximum instantaneous valve can be up to 30 %. The average COP of heating conditions was 2.66 with a droop rate of 11.3% relative to the rated COP. The average COP of operation cycle containing defrosting was 2.37 with a droop rate of 20.9% relative to the rated COP. Power consumption of defrosting was 9.2% of the total power consumption. Without defrosting, the maximum of the instantaneous heating capacity was almost 94% -98% of the rated valve. Heating capacity changes caused by different wind speeds of indoor unit was about 4%. It' s proved that outdoor unit working in the frosting condition is the main reason of heating capacity and COP declining. The advanced defrosting measure is the key to diminish the influence of frosting and improve the operating efficiency.
出处 《太阳能学报》 EI CAS CSCD 北大核心 2010年第12期1580-1584,共5页 Acta Energiae Solaris Sinica
基金 "十一五"国家科技支撑计划(2006BAJ01A05) 重庆大学高层次人才启动基金(0903005104986)
关键词 空气源热泵 夏热冬冷地区 极端天气 适应性 air source heat pump hot summer and cold winter areas extreme weather adaptability
  • 相关文献

参考文献8

  • 1清华大学建筑节能研究中心.中国建筑节能年度发展研究报告2007[M].中国建筑工业出版社,2007.
  • 2清华大学建筑节能研究中心.中国建筑节能年度发展研究报告2008[M].北京:中国建筑工业出版社,2008.
  • 3GB/T7725-2004.房间空气调节器[S].[S].,..
  • 4方修睦.建筑环境测量技术[M].北京:中国建筑工业出版社,2000,144-145.
  • 5Byun J S,Lee Jinho,Jeon C D.Frost retardation of an airsource heat pump by the hot gas bypass method[J].International Journal of Refrigeration,2007,(05):1-7.
  • 6罗鸣,谢军龙,沈国民.风冷热泵机组中的热气除霜方法[J].制冷与空调,2003,3(6):47-49. 被引量:9
  • 7许东晟,陈汝东.除霜和除霜控制研究[J].流体机械,2006,34(1):69-73. 被引量:27
  • 8陈颖,李筱萍.热泵型空调器结霜除霜的判定[J].暖通空调,2001,31(6):44-46. 被引量:16

二级参考文献14

  • 1程建杰,陈汝东.制冷装置的除霜研究[J].流体机械,2004,32(7):64-66. 被引量:16
  • 2张祉佑.制冷原理与设备[M].北京:机械工业出版社,1986..
  • 3卢士勋.制冷与空气调节技术[M].上海:上海科学普及出版社,1991.190-194,209-225.
  • 4安立正明ら.ヒ-トポソプ式ル-ムェアコソにぉける着霜现象につぃて[J].冷冻,152(598):29-35.
  • 5Al - Mutawa, NawafK. Sherif, S A. Analytical model for hot - gas defrosting of a cylindrical coil cooler: Part Ⅱ - model results and conclusions [Conference Paper]ASHRAE Transactions. v 104 n Pt 1B 1998. ASHRAE, Atlanta,GA, USA. p1731~1737 SF-98- 27- 3.
  • 6Al - Mutawa, NawafK. Sherif, S A. Analytical model for hot - gas defrosting of a cylindrical coil cooler: Part Ⅰ - model development [ Conference Paper]ASHRAE Transactions. v 104 n Pt 1B 1998. ASHRAE, Atlanta, GA, USA. p 1722~1729 SF-98- 27- 2.
  • 7Strong, Arthur P. Hot Gas defrost of industrial refrigeration. [Journal Article]Heating, Piping & Air Conditioning. v 60 n 7 Jul 1998 p 71 ~83.
  • 8陈汝东,许东晟.风冷热泵空调器除霜控制的研究[J].流体机械,1999,27(2):55-57. 被引量:33
  • 9黄虎,李志浩,束鹏程.风冷热泵除霜控制方法分析[J].建筑热能通风空调,1999,18(3):38-40. 被引量:11
  • 10石文星,李先庭,邵双全.房间空调器热气旁通法除霜分析及实验研究[J].制冷学报,2000,21(2):29-35. 被引量:82

共引文献152

同被引文献112

引证文献12

二级引证文献54

相关作者