期刊文献+

房间空调器热气旁通法除霜分析及实验研究 被引量:82

Exeprimental Research on Hot Vapor Bypass Defrosting Method
在线阅读 下载PDF
导出
摘要 通过对不同阻力的旁通电磁阀除霜进行实验研究 ,热气旁通法除霜可以较大程度地改善室内舒适性 ,旁通电磁阀的阻力大小直接影响着换热器除霜时间和除霜效果。经分析表明 ,采用电子膨胀阀和旁通电磁阀组合除霜不仅有良好的节能效果 ,还可较大程度地缩短除霜时间 ;压缩机吸气管温度大于 0℃可作为结束除霜的判据之一。 Different electromagnetic valves are used to research the performance of defrosting.Experimental results show that the resistance of valve has a direct influence on the time and effect of defroing.As well,indoor thermal comfort can be increased greatly when hot vapor bypass method is used to defrost.Not only the effect of defrosting is increased but also the time of defrosting is shortened when electronic expansion valve and bypass electromagnetic valve are used together.It indicates the frost has been cleaned that the temperature at inlet of compressor is higher than 0℃.
出处 《制冷学报》 CAS CSCD 北大核心 2000年第2期29-35,共7页 Journal of Refrigeration
关键词 热气旁通 除霜 换热器 电磁阀阻力 房间空调器 Hot vapor bypass,Defrosting,Heat exchanger,Resistance of electromagnetic valve,Comfort
  • 相关文献

参考文献4

  • 1[1]Sousuke Fujimuki, Tatuo Tanaka. Inverter Room Air Conditioners, REFRIGERATION , Vol. 61, №701, pp31-35,1986
  • 2[2]Hirokiyo terada, Naoshi Uchikawa, Kensaku Oguni.Hitachi Package Air Conditioner With Scroll Compressor,REFRIGERATION, Vol. 60, №693, pp1 1 - 20,1985
  • 3[3]Yoshinobu Yamazaki. Inverter Air- Conditioners with Thermal Storage Unit and Fuzzy Logic Control System.REFRIGERATION, Vol. 67, No 772, PP14 - 22,1992
  • 4[4]Masami Hayashi, Shigeru Nariai, Masaya Hayama.Develoment of Scroll Inverter Air Conditioners, REFRIGERATION, Vol. 67, №772, pp51 - 57,1992