济宁市公共场所集中空调通风系统污染调查 被引量:1

Pollution Investigation of Centralized Air Ventilation System in Public Places of Jining City
原文传递
导出
摘要 目的了解济宁市集中空调通风系统的卫生状况,提出合理化建议,保障人体健康。方法采用随机抽样调查,依据《公共场所集中空调系统卫生规范》对空调系统的通风量、管道积尘等指标进行采样检测。结果检测的28家单位中均没有进行专业清洗,经卫生学检测管道积尘合格率69.19%,细菌总数合格率43.60%,真菌总数合格率27.91%。经统计学分析,各单位间积尘量合格率间差异无统计学意义(χ2=4.902,P>0.05);各单位间细菌总数合格率间差异有统计学意义(χ2=33.627,P<0.05);各单位间真菌总数合格率间差异有统计学意义(χ2=18.957,P<0.05)。结论济宁市集中空调系统存在很大的安全隐患,应加大卫生监督力度,进行宣传教育,保障人体健康。 Objective To know the sanitary condition of the centralized air ventilation system in public places of Jining city,make the reasonable suggestions and ensure people's health.Methods Air samples were collected by randomized sampling,and detected the hygiene indexes based on Specification for Hygiene Management Central Air Conditioning Ventilation System of Public Place.Results There was no one unit to clean the centralized air conditioning system in the 28 wits.The qualified rates of pipeline dust,bacterium and total fungi were 69.19%,43.60% and 27.91%.There was no significant difference in the qualified rates of pipeline dust(χ2=4.902,P0.05) among the 28 units,there were significant differences in the qualified rates of bacterium(χ2=33.627,P0.05) and of the total fungi(χ2=18.957,P0.05) among different types of units.Conclusion Centralized air conditioning system exists serious safety risk in public places of Jining.Sanitary supervision should be strengthened,publicity and education will be developed to ensure people's health.
出处 《中国卫生工程学》 CAS 2010年第6期452-453,455,共3页 Chinese Journal of Public Health Engineering
关键词 集中空调系统 公共场所 卫生状况 Central air conditioning system Public place Sanitary condition
  • 相关文献

参考文献4

二级参考文献17

  • 1杨翠婵,陆也民.空调办公室环境质量与人群健康状况的调查[J].广东卫生防疫,2001,27(1):58-59. 被引量:8
  • 2梁惠宁.空调客房与非空调客房的卫生学调查[J].环境与健康杂志,1996,13(3):127-127.
  • 3Backman-H, Haghighat-F. Indoor air quality and ocular discomfort[J] .J AM optom Assoc, 1999, 70(5) :309 - 316.
  • 4Nordstrom K, Norback D, Akselsson R. Effect of air humidification on the sick building syndrome and perceived indoor air quality in hospitals: A four month longitudinal study [J ]. Occup Environ Med, 1994, 51(10) :683 - 688.
  • 5Keller DW.Community Outbreak of Legionnairesp disease:an investigation confirmingthe potential for coolingtowers totransmit legionella species[J].Clin Infect Dis,1996,22:2572261.
  • 6Keller BW,Hajjeh R,Maria AD,et al.Community outbreak of Legionnaires'disease:An investigation confirming the potential for cooling tower to transmit Legionella species[J].Clin Infect Dis,1996,22:2572261.
  • 7Dondero TJ,Rendorff RC,Mallison GF,et al.An outbreak of Legionnaires'disease asociateel with a contaminated air conditioning cooling tower[J].N Engl J Med,1980,302:3652370.
  • 8刘建军.深圳市1998 1999年流行性感冒监测[J].中华流行病学杂志,2001,22(2):158-159.
  • 9环境与健康杂志编辑部.世界卫生组织公布香港淘大花园SARS传播的环境卫生报告.环境与健康杂志,2003,20(4):245-245.
  • 10夏正英,佘德宏,赵霞.扬州市新装饰开业公共场所甲醛污染状况[J].环境与健康杂志,2000,17(5):287-289. 被引量:15

共引文献125

同被引文献3

引证文献1

二级引证文献3

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部