一起220kV GIS设备故障跳闸原因分析 被引量:4

Cause Analysis on One Fault Trip of 220kV GIS Equipment
在线阅读 下载PDF
导出
摘要 介绍一起220 kV GIS设备发生W相线路侧接地故障造成三相开关跳闸的情况,通过故障检查认为,跳闸是由设备内部绝缘件表面附着油迹,造成设备在运行中发生内部闪络放电引起的,通过深入分析设备内部绝缘件表面出现油迹和发生绝缘击穿的原因,提出加强设备安装与运行维护中对抽真空设备管理的建议。 This paper introduces the situation of three-phase switch trip caused by earthing fault of W-phase line-side of a 220 kV GIS equipment.By the fault test result,that trip was due to the oil attached to the surface of the internal insulated part,leading to internal flashover discharge during the operation,analyzes in-depth the cause of the oil attached to the surface of the equipment internal insulated part and insulation breakdown occurred,and proposes the improvement for strengthening the equipment installation and the management of the vacuum equipment during the operation maintenance.
机构地区 石家庄供电公司
出处 《河北电力技术》 2010年第4期49-51,共3页 Hebei Electric Power
关键词 GIS 接地故障 油迹 闪络放电 盆式绝缘子 真空泵 GIS earthing fault oil flashover discharge basin-type insulator vacuum pump