期刊文献+

交流滤波器高压电容器保护及其跳闸原因分析 被引量:4

Analysis of Protection for High Voltage Capacitor of AC Filter and Cause of Tripping Operation
在线阅读 下载PDF
导出
摘要 介绍了天生桥换流站交流滤波器高压电容器的构成,基于高压电容器不平衡保护原理总结了不平衡保护的优缺点,并分析了外部环境参数对电容器电容值的影响。以C型交流滤波器不平衡保护跳闸原因为例,提出了相应的整改措施,供借鉴。 This paper introduces the structure of high voltage capacitor of AC filter in Tianshengqiao converter station. The merit and demerit of unbalance protection is summarized by the principle of unbalance protection for high-volt- age capacitor. The effect of external environment parameters on the capacitance is analyzed. Taking the cause of unbalance protection tripping operation for C type AC filter for an example,it brings forward the solution method and provides reference for similar engineering project.
出处 《水电能源科学》 北大核心 2010年第3期143-145,共3页 Water Resources and Power
关键词 交流滤波器 高压电容器 不平衡保护 外部环境 跳闸 AC filter high-voltage capacitor unbalance protection external environment tripping operation
  • 相关文献

参考文献4

二级参考文献6

  • 1Tianguang TCSC at Pingguo:protection coordination for TCSCsegment protection.SIEMENS,2002.
  • 2Tianguang TCSC at Pingguo:protection coordination for FSC segment protection.SIEMENS,2002.
  • 3Hechi series capacitor:protection coordination.SIEMENS,2003.
  • 4Capacitor unbalance CT accuracy analysis report.GE,2004.
  • 5C/P software design report for Anshun and Zhaoqing station.SIEMENS,2002.
  • 6C/P software design report for TSQ and guangzhou station,SIEMENS,1997.

共引文献47

同被引文献24

引证文献4