期刊文献+

基于IEC61850的SF_6断路器在线监测系统的信息建模及通信实现 被引量:17

Information modeling and communication of SF_6 circuit breaker on-line monitoring system based on IEC61850
在线阅读 下载PDF
导出
摘要 针对高压断路器SF6断路器状态在线监测的特点,提出合理利用IEC61850标准中逻辑节点GGIO,应用IEC61850对实际智能电子设备(IED)进行建模;断路器状态在线监测数据通过GOOSE报文传输,GOOSE采用发布/订阅模式,报文延迟不超过4ms。论述了GOOSE报文的组织方式及通信机制;选用实时性高的操作系统VxWorks,并在其Tomado编译调试环境下,运用VC++编写了模型通信程序,给出了分析程序的主要功能函数及流程图。 According to the characteristics of SF6 circuit breaker state on-line monitoring, it is proposed to fully use the logical node GGIO(Generic Input / Output) of IEC61850 in the modeling of intelligent electronic devices. The on-line monitoring data of circuit breaker state is transferred by GOOSE (Generic Object Oriented Substation Event) message with time delay less than 4 ms,which applies publish/subscribe model, its scheduling and communications mechanism are introduced. VxWorks, an operating system by excellent real-time performance is selected and the model communication program is written by VC++ in its Tornado compiler debugging environment. The main functions and flowcharts of analysis program are given.
出处 《电力自动化设备》 EI CSCD 北大核心 2010年第2期131-134,共4页 Electric Power Automation Equipment
关键词 SF6断路器 状态在线监测 IEC61850模型 GOOSE 应用程序 SF6 circuit breaker on-line state monitoring IEC61850 model GOOSE application program
  • 相关文献

参考文献9

二级参考文献33

  • 1殷志良,刘万顺,杨奇逊,秦应力.一种遵循IEC 61850标准的合并单元同步的实现新方法[J].电力系统自动化,2004,28(11):57-61. 被引量:102
  • 2殷志良,刘万顺,秦应力,杨奇逊.一种基于FPGA技术的电子式互感器接口实现新方法[J].电力系统自动化,2004,28(14):93-96. 被引量:53
  • 3张可畏,王宁,段雄英,邹积岩,黄智宇.用于电子式电流互感器的数字积分器[J].中国电机工程学报,2004,24(12):104-107. 被引量:110
  • 4陈玉 吕一航 成永红 等.中压开关柜绝缘特性在线检测技术的研究[A]..第5届全国智能化电器及应用研讨会[C].西安,2001..
  • 5LJJAbrosse.Embeded System Buliding Blocks[M].北京:机械工业出版社,2002..
  • 6方可行.断路器故障与监测[M].北京:中国电力出版社,2002..
  • 7Y Han, Y H Song. Condition Monitoring Techniques for Electrical Equipment A Literature Survey[J]. IEEE Trans on Power Deliver, 2003, 18(1):4-13.
  • 8C. Sweetser, Bergman, G. MontiUet, et al. Strategies for selecting monitoring of circuit breakers. IEEE Transactions on power delivery, VOL. 17. No. 3, July 2002.
  • 9Brunner C, Schimmel G, Schubert H. Standardization of serial links replacing parallel wiring to transfer process data [C]. 34-209, CIGRE, Paris, France, 2002: 34-209.
  • 10IEC61850-7-2 Communication networks and systems in substationspart 7-2: Basic communication structure for substation and feeder equipment- Abstract communication service interface[S]. 2003.