摘要 在室外环境空气温度-15℃~5℃、相对湿度65%-90%范围内,对一台空气源热泵室外换热器表面霜层生长特性及热泵系统动态性能进行了实验研究。实验结果表明,翅片表面霜层厚度呈分段增长模式,在结霜初始段,霜层主要由粒状冰晶组成,并逐渐形成柱状冰晶,其厚度增长较快;在第二阶段为柱状冰晶主要在其半径方向生长,霜层厚度增长速度减慢;而在第三阶段,柱状冰晶主要在其高度方向生长,逐渐形成针状冰晶,霜层厚度增长速度迅速增大至第二阶段的3-5.8倍。对实验结果的分析表明,热泵机组性能恶化主要是由于蒸发器表面温度下降、霜晶形态变化引起霜层厚度快速增长及空气流动阻力增加导致风机流量下降三个因素之间形成的恶性循环所致,其中换热器表面温度下降引起的霜晶形态变化起到了至关重要的作用。 The frost growth characteristics on the outdoor heat exchanger and the dynamic performance of an air source heat pump (ASHP) were experimentally investigated. The experimental outdoor air temperature ranged from -15℃ to 5℃, and relative humidity was from 65% to 90%. The results indicate that the frost grew in three stages. In the initial stage, the granular ices grew on the surface, and then the column-shaped ice crystals were formed gradually and the frost thickness rose quickly. After the first stage, the column-shaped ice crystals grew in its radius rather than in its length, and thus the growth rate of frost thickness decreased with the frosting time. In the third stage, the column-shaped ice crystals grew mainly in its length and the ice crystals had the acerose shape gradually, and the growth rate of frost thickness increased rapidly to 3-5.8 times that in the second stage. It is found that the performance degradation of the ASHP unit was caused by the wall temperature drop of the evaporator, the rapid increase in the frost thickness, and the decrease in the air flow rate.
出处 《制冷学报》 CAS CSCD 北大核心 2010年第1期18-22,共5页 Journal of Refrigeration
基金 天津市应用基础研究计划(06YFJMJC05500)资助~~
关键词 工程热物理 空气源热泵 霜层生长特性 动态性能 结霜实验 Engineering thermophysics Air source heat pump Frost growth characteristics Dynamic performance Frosting experiment
  • 相关文献

参考文献18

  • 1Kondepudi S N, O' Neal D L. Effect of frost growth on the performance of louvered finned tube heat exchangers [J]. Int J Refrigeration, 1989, 12 (3):151-158.
  • 2Kondepudi S N, O' Neal D L. Performance of finnedtube heat exchangers under frosting conditions: part II. Comparison of experimental data with model[J]. Int J Refrigeration. 1993, 16 (3): 181-184.
  • 3Yan W M, Li H Y, Wu Y J, et al. Performance of finned tube heat exchangers operating under frosting conditions [J]. Int J Heat Mass Transfer, 2003, 46 (5) : 871-877.
  • 4Yah W M, Li H Y, Tsay Y L. Thermofluid characteristics of frosted finned-tube heat exchangers[J]. Int J Heat Mass Transfer, 2005, 48 (15) : 3073-3080.
  • 5Xia Y, Zhong Y, Hrnjak P S, et al. Frost, defrost, and refrost and its impact on the air-side thermal-hydraulic performance of louvered-fm, fiat-tube heat exchangers[J]. Int J Refrigeration, 2006, 29 (6) 1066-1079.
  • 6Yang D K, Lee K S, Song S. Modeling for predicting frosting behavior of a fin-tube heat exchanger[J]. Int J Heat and Mass Transfer, 2006, 49 (7-8) :1472-1479.
  • 7Seker D, Karatas H, Egrican N. Frost formation on fin-and tube heat exchanges. Part I: Modeling of frost formation on fin-and tube heat exchangers[J]. Int J Refrigeration, 2004, 27 (4) : 367-374.
  • 8Yao Y, Jiang Y Q, Deng S M. A study on the performance of the airside heat exchanger under frosting in an air source heat pump water heater/chiller unit[J]. Int J Heat and Mass Transfer, 2004, 47 (17-18): 3745-3756.
  • 9Tso C P, Cheng Y C, Lai A C K. Dynamic behavior of a direct expansion evaporator under frosting condition. Part I: Distributed model[J]. Int J Refrigeration, 2006, 29 (4) 611-623.
  • 10Miller W A. Laboratory examination and seasonal analysis of frosting and defrosting for an air-to-air heat pump[J]. ASHRAE Trans, 1987, 93 (1) :1474-1489.

二级参考文献20

  • 1姬长发,黄东,袁秀玲.风冷热泵冷热水机组结霜与除霜性能的实验研究[J].西安交通大学学报,2005,39(5):480-484. 被引量:13
  • 2郭宪民,王成生,汪伟华,陈纯正.结霜工况下空气源热泵动态特性的数值模拟与实验验证[J].西安交通大学学报,2006,40(5):544-548. 被引量:35
  • 3Nutter D W, O'Neal D L, Payne W V. Impact of the suction line accumulator on the frost/defrost performance of an air-source heat pump with a scroll compressor[J]. ASHRAE Transaction, 1993,99(1):689-698.
  • 4O'Neal D L, Peterson K T, Anand N K.Effect of short-tube orifice size on the performance of an air source heat pump during the reverse-cycle defrost[J]. Int J Refrig, 1991, 14(7):52-57.
  • 5Huelle Z R. The MSS line-a new approach to the hunting problem[J]. ASHRAE Journal, 1972, 14(8): 43-46.
  • 6Ogawa K,Tanaka N,Takeshita M.Performance improvement of plat fin-and-tube heat exchangers under frosting conditions [J].ASHRAE Trans,1993,99(1):762-771.
  • 7Yao Y,Jiang Y Q,Deng S M,A study on the performance of the airside heat exchanger under frosting in a air source heat pump water heater/chiller unit [J].Int J of Heat and Mass Transfer,2004,47(17-18):3745-3756.
  • 8Chen H,Thomas L,Besant R W.Fan supplied heat exchanger fin performance under frosting conditions [J].Int J Refrig,2003,26(1):140-149.
  • 9Yasuda H,Senshu T,Kuroda S,et al.Heat pump performance under frosting conditions:simulation of heat pump cycle characteristics under frosting conditions [J].ASHRAE Trans,1990,96(1):330-336.
  • 10Senshu T,Yasuda H,Kuroda S,et al.Heat pump performance under frosting conditions:Part I-Heat and mass transfer on cross-finned tube heat exchangers under frosting conditions[J].ASHRAE Trans,1990,96:324-329