期刊文献+

结霜工况下空气源热泵动态特性的数值模拟与实验验证 被引量:35

Numerical Simulation and Experimental Verification on Dynamic Performance of Air Source Heat Pump under Frosting Conditions
在线阅读 下载PDF
导出
摘要 对结霜工况下空气源热泵的动态特性进行了数值模拟,并在室外环境空气温度及相对湿度分别为-15~3℃和50%~90%范围内对一台空气源热泵空调器的动态性能进行了实验研究,测量了不同结霜工况条件下热泵空调器的动态性能参数、室外换热器结霜量及壁面温度分布.在此基础上分析了进风温、湿度对空气源热泵空调器性能的影响.实验结果表明:在室外换热器表面结霜的初始阶段,热泵系统的制热量及性能系数均有所提高,但在结霜的后期,热泵性能迅速衰减,与数值预测结果一致;对于相对湿度不同的进口空气,其温度为0~3℃时室外换热器表面结霜速度最快,在此温度范围内结霜对热泵性能影响最大. Regarding the frost accumulation on the outdoor coils as a quasi-dynamic process, the dynamic performances of an air source heat pump (ASHP) system under frosting conditions were simulated. A series of experiments on the dynamic performance of the ASHP unit under frosting conditions were conducted to verify the present simulation model. The experimental outdoor air temperature ranged from --15℃ to 7 ℃, and the relative humidity from 50% to 90%. The dynamic performance parameters of the ASHP system under frosting conditions, the frost mass accumulation on the outdoor coils, and the wall temperature distribution along the heat exchange tubes were measured. Based on the experimental results, the effects of the outdoor air temperature and the relative humidity on the performance of ASHP unit were analyzed. The experimental results indicate that the heating capacity and coefficient of performance of the ASHP unit increase in the initial frosting stage and decrease rapidly in the later frosting stage. These experimental resuits are in good agreement with the corresponding simulation ones. In addition, it is found that the frost formation rate is greatest when the outdoor air temperature is about 0-30C at different outdoor air relative humidities.
出处 《西安交通大学学报》 EI CAS CSCD 北大核心 2006年第5期544-548,共5页 Journal of Xi'an Jiaotong University
关键词 空气源热泵 结霜工况 动态特性 air source heat pump frosting condition dynamic characteristics
  • 相关文献

参考文献7

二级参考文献14

  • 1刘维华,白梓运,陈芝久.膨胀阀动态响应特性的实验研究[J].流体机械,1995,23(7):60-62. 被引量:1
  • 2丁国良.小型制冷装置动态仿真与优化研究[学位论文].上海:上海交通大学动力系,1993..
  • 3黄虎,能源技术,1998年,4期,35页
  • 4蒋能照,空调用热泵技术及应用,1997年,126页
  • 5丁国良,学位论文,1993年
  • 6Krakow K I,ASHRAE Trans,1992年,98卷,1期,462页
  • 7Nutter D W, O'Neal D L, Payne W V. Impact of the suction line accumulator on the frost/defrost performance of an air-source heat pump with a scroll compressor[J]. ASHRAE Transaction, 1993,99(1):689-698.
  • 8O'Neal D L, Peterson K T, Anand N K.Effect of short-tube orifice size on the performance of an air source heat pump during the reverse-cycle defrost[J]. Int J Refrig, 1991, 14(7):52-57.
  • 9Huelle Z R. The MSS line-a new approach to the hunting problem[J]. ASHRAE Journal, 1972, 14(8): 43-46.
  • 10黄虎,束鹏程,李志浩.中央空调系统的节能与能源合理利用[J].能源技术,1998(3):46-49. 被引量:4