期刊文献+

交流特高压避雷器用监测器动作特性研究 被引量:15

Research on the Action Characteristics of the Monitors Used for the UHV Metal-oxide Surge Arrester
在线阅读 下载PDF
导出
摘要 为了判断特高压避雷器的运行工况,针对国家电网公司特高压交流试验基地的情况,在4次1000kV变压器投合的背景下,对6相特高压避雷器用监测器的动作次数和电流进行了分析。分析表明,晋东南—荆门1000kV特高压交流试验示范工程1000kV瓷外套式金属氧化物避雷器技术协议中提出的监测器的下限动作电流难以正确反应避雷器实际运行工况,为此提出了监测器门槛动作电流的新概念并明确了门槛动作电流的区间范围,按此原理调整监测器将能更准确的动作,更利于特高压避雷器的运行工况判断。 For judging the operating condition of the Ultra-High-Voltage arresters, the overvoltage level in the AC Ultra-High-voltage test base of SGCC is researched. In the background of 1000 kV transformer switching on for four times, the action times and the current of the 6 phases of the Ultra-High-Voltage arrester monitor are researched. It is showed that according to 1000 kV porcelain Metal-Oxide-Arresters technology agreement of the Jindongnan-Jingmen 1000 kV Ultra-High Voltage AC testing demonstration project, it is difficult to judge the real act condition of the monitor by the lower limit of the action current. A new concept of current threshold for the monitor is proposed and the range of monitor of the threshold action current is suggested. By this principle, the new designed monitor will he able to act more accurately. It is more beneficial to judge the operating condition of the Ultra- High-Voltage arresters.
出处 《高电压技术》 EI CAS CSCD 北大核心 2008年第11期2295-2299,共5页 High Voltage Engineering
基金 国家电网公司重点科技项目(SGTGY[2008]614)~~
关键词 特高压 MOA 监测器 TOV 动作特性 门槛动作电流 UHV MOA monitor TOV action characteristics threshold action current
  • 相关文献

参考文献13

二级参考文献38

共引文献172

同被引文献166

引证文献15

二级引证文献99

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;