期刊文献+

基于虚拟仪器的电力系统动态模拟实验数字化改造 被引量:3

The Digital Change of Power System Dynamic Analog Laboratory Based on Virtual Instrumentation
在线阅读 下载PDF
导出
摘要 由于现有的纯物理动态模拟实验室已经难以满足现代电力系统实验教学要求,本文提出基于虚拟仪器的动态模拟实验数字化改造方案。以动态模拟实验中的"同步发电机三相突然短路电流测参数"的数字化改造为例,利用LabVIEW中的Prony分析工具对同步发电机三相短路电流进行分析,得到各个模态的信息,进而根据短路电流公式对发电机的参数进行辨识,并与传统上下包络线法作比较,说明Prony算法的有效性和数字化改造的可行性。 The laboratory of dynamic analog has already not satisfied so many requirements of the modern power system experiment teaching,the digital change of dynamic analog laboratory based on virtual instrumentation is put forward in this paper.Through the method of Prony,the sudden shorted circuit current waveforms are analyzed for three phase synchronous generator.Using the outcome of the analysis,we identify the parameters of the synchronous generator.Compared with primary,we prove the validity of the Prony arithmetic and the feasibility of the digital change.
作者 赵成勇
出处 《电气电子教学学报》 2008年第1期87-90,共4页 Journal of Electrical and Electronic Education
关键词 动态模拟实验 短路电流 PRONY算法 参数辨识 dynamic analog experiment short-circuit current Prony method parameters identification
  • 相关文献

参考文献4

二级参考文献14

  • 1严亚勤,吴文传,张伯明.基于嵌入式Linux的网络RTU[J].电力自动化设备,2004,24(9):27-29. 被引量:12
  • 2[1]Hauer JF, et al. Initial results in Prony analysis of power system response signals. IEEE Trans. on Power Systems, 1990, 5 (1)
  • 3[2]Trudnowski D J, et al. An application of Prony methods in PSS design for multimachine systems. IEEE Trans. on Power Systems, 1991, 6 (1)
  • 4[3]Smith J R, et al. Transfer function identification in power system applications. IEEE Trans. on Power Systems, 1993, 8 (3)
  • 5[4]Hauer J F, et al. Application of Prony analysis to the determination of modal content and eqivalent models for measured power system response. IEEETrans. on Power Systems, 1991, 6 (3)
  • 6[5]Kumaresan R, et al. A Prony method for noisy data:Choosing the signal components and selecting the order in exponential signal models. Proc. of IEEE, 1984, 72 (2)
  • 7[6]Kumaresan R, et al. Estimating the parameters of exponentially damped sinuscids and pole-zero nodeling in ncise. IEEE Trans.on Acoustics, Speech and Signal Processing, 1982, 30 (1)
  • 8[7]Trudnowski D J. Making Prony analysis more accurate using multiple signals. IEEE Transactions on Power System,February 1990, 14 (1)
  • 9[8]Chen C, Xu B, Gou B. Identifying parameters of DAVR by Prony analysis. Proc. of ICEE'96, Beijing 1996.
  • 10J.E Hauer. Application of Prony Analysis to the Determination of Modal Content and Equivalent Models for Measured Power System Response[J].IEEE Transactions on Power Systems, 1991, 6(1):1062-1068.

共引文献42

同被引文献20

引证文献3

二级引证文献5

相关作者