地铁变风量环控系统全年运行方案研究 被引量:5

Study on VAV-based Year-round Operation Mode for Environmental Control in the Subway
原文传递
导出
摘要 通过对地铁车站公共区的热负荷进行分析计算,确定了远期地铁车站公共区逐时通风量,结合天津市地铁1号线环控系统的设计方案,提出了空调风机全年变频运行,并用计算流体力学(CFD)模拟的方法,借助Airpak软件,模拟夏季车站变风量运行时车站公共区的温度场和速度场,得出变风量运行后能够达到的设计要求。 Based on the calculated cooling load of common area in the subway station, the hourly ventilation rate could be determined. Combined with the design plan of 1 # line of Tianjin Subway, the year-round frequency control strategy for the fan was put forward. In addition, using the CFD technology and Airpak software, the velocity and temperature fields under the VAV-based operation mode in the common area in summer were simulated. Finally, it was found out that the related results could satisfy the design requests.
出处 《建筑科学》 北大核心 2007年第4期87-94,共8页 Building Science
关键词 地铁环境控制 变风量系统 CFD技术 全年运行方案 subway environmental control VAV system CFD year-round operation mode