期刊文献+

XLPE电缆绝缘接头局放在线检测方法探讨 被引量:18

Study on the Method of PD On-line Detection of XLPE Cable Insulating Joints
在线阅读 下载PDF
导出
摘要 用基于电磁耦合法的VHF宽频带钳型电流传感器配合基于阿基米德螺旋天线的UHF传感器的方法研究了在线检测带有交叉互联线的XLPE电缆绝缘接头局部放电。该法对电缆绝缘接头处VHF和UHF信号的时域和频域分析可有效地识别被测电缆绝缘接头部内、外部的局放信号。VHF和UHF检测技术相互配合联合降噪可有效抑制宽带脉冲干扰,实验室和现场试验证明该法效果较好。 In this paper, a method of PD on-line detection of XLPE cable insulating joints is developed, using two VHF clamp current transducers and an UHF sensor. This method analyzes VHF and UHF signal of detected cable joint, using time and lating joint. Using V Tests prove that this frequency analysis. This method can be used for detecting PD pulse inside or outside the insulating joint.Using VHF and UHF techniques, this method can easily discriminate PD from noise. Lab and on-site method has a good effect of detection.
作者 韦斌 李颖
出处 《高电压技术》 EI CAS CSCD 北大核心 2005年第10期30-32,共3页 High Voltage Engineering
关键词 XLPE电缆 绝缘接头 局部放电 在线检测 XLPE cable insulating joint PD on-line detection
  • 相关文献

参考文献12

二级参考文献15

  • 1[1]Ohki Y. Present stage of partial discharge monitoring tecnique in after-laying tests for extra-high voltage XLPE cable lines. IEEE Magazine Electrical Insulation, 2000,16(1):74
  • 2[2]Gulski E, Wester F J, Smit J J et al. Advanced partial discharge diagnostic of MV powr cable system using oscillating wave test system. IEEE Magazine Electrical Insulation, 2000,16(2):17
  • 3Junhua Luo, et al. Study on surface discharge of composite dielectric in XLPE power cable joints[A]. 25th Anniversary Electrical Insulation Conference [ C ].Cincinnati, USA, 2001.
  • 4刘耀南 邱昌容.电气绝缘测试技术[M].北京:机械工业出版社,1990..
  • 5Ginzo Katsuta, Atsushi Toya, Keiichi Muraoka, et al, Development of a method partial discharge detection in extra-high voltage cross-linked polyethylene insulated cable lines[J]. IEEE Trans on Power Delivery, 1992. 7(3): 1068-1074
  • 6Wenzel D, Schichler U, Borsi H, et al. Recognition of partial discharges on power units by directional coupling[C]. The 9th ISH. Austria, 1995,5626: 1-4
  • 7Borsi H, G-ockenbach E, Schichler U. Monitoring of partial discharges (PD) in high voltage cables[C] The 8th ISH. Japan, 1993: 173-176
  • 8Wouters P A A F, Vanderlaan P C T, Hetzel E, et al. New on-ine partial discharge measurement technique for polymer insulated cables and accessories[C]. The 8th ISH. Japan, 1993:105-108
  • 9IEC60270. Partial discharge measurements[S], 1981
  • 10Ahmed N H, srinivas N N. On-line partial discharge detection in cables [J]. IEEE Trans on D & El, 1998, 5(2) : 181-188

共引文献315