期刊文献+

小电流接地电网改进能量法接地选线原理 被引量:23

Improved energy function to detect the grounded line in neutral point indirectly grounded network
在线阅读 下载PDF
导出
摘要 根据小电流接地电网单相接地故障时电压电流的变化特点,利用中性点电压、故障相电压和零序电流构造的能量曲线的斜率来进行故障选线。该方法不受电网平衡情况和接地电阻大小的影响,对复杂的间歇性电弧接地故障同样有效。MATLAB仿真证明了本文的结论是正确的。 In this paper, a new method of energy function to detect single-phase earth fault in neutral point indirectly grounded network is presented. This method is based on the slope of energy curve constructed by neutral voltage, fault phase voltage, and zero-sequence current to detect the fault line. It is immune from the unbalanced status of network and the values of earthed resistance. To the complicated intermittent arc-earth fault, the proposed method also works well. MATLAB simulation verifies the points of the paper.
作者 朱丹 蔡旭
出处 《继电器》 CSCD 北大核心 2004年第10期44-48,共5页 Relay
关键词 小电流接地系统 消弧线圈 电网 数学模型 能量法 选线原理 neutral point indirectly grounded network intermittent arc-earth fault zero-sequence energy
  • 相关文献

参考文献6

  • 1马珂,张保会.中性点非直接接地系统故障选线原理的发展与展望[J].继电器,2003,31(5):65-70. 被引量:56
  • 2Seppo Hanninen, Matti Lehtonen. Characteristics of Earth Faults in Electrical Distribution Networks with High Impedance Earthing [J]. Electric Power Systems Research,1998,44.
  • 3李福寿(LI Fu-shou).中性点非有效接地电网的运行(Performance of Electrical Network with Neutral Point Un-efficient Grounding) [ M ].北京:水利电力出版社(Beijing:Hydraulic and Electric Power Press), 1993.
  • 4要焕年,曹梅月(YAO Huan-nian, CAO Mei-yue).电力系统谐振接地(Power System Harmonic Oscillation Grounding) [ M ].北京:中国电力出版社( Beijing: China Electric Power Press),2000.
  • 5何奔腾,胡为进.能量法小电流接地选线原理[J].浙江大学学报(自然科学版),1998,32(4):451-457. 被引量:91
  • 6Griffel D, Harmand Y,Leitloff V,et al. New Deal for Safety and Quality on MV Networks[J]. IEEE Trans on Power Delivery, 1997,12(4).

二级参考文献24

共引文献142