摘要
选用抚州供电局上顿渡2号主变油样,对防止变压器油质劣化进行了多项试验,并将此试验结果应用于该主变油中。根据一年来的实际使用效果,得出对于油中T501含量很低的变压器油,只要补加0.3%剂量的T501抗氧化剂,就可以取得优良的防劣化效果。
A lot of testing of preventing the transformer oils ageing was processed with Shangdundu No.2 transformer oil in Fuzhou power-supply institute, and the experiment result would be used in the transformer oil. On the base of the using result nearby one year it is educed that when T501 dosage in the transformer oils is very lower as long as 0.3%T501 oxidation inhibitor dosage is filled a good effect of preventing transformer oils ageing will be obtained.
出处
《江西电力》
2004年第1期26-28,共3页
Jiangxi Electric Power