期刊文献+

基于超高频检测技术研究GIS中的局部放电 被引量:12

RESEARCH ON PARTIAL DISCHARGE IN GIS BASED ON UHF METHOD DETECTION
在线阅读 下载PDF
导出
摘要 根据气体绝缘的金属封闭式组合电器(GIS)的波导结构及局部放电脉冲所激发的电磁波的宽频带特征,建立了外部天线超高频局部放电检测系统。利用该系统对252 kV GIS母线段中相同气压、不同电压超高频下固定微粒局部放电模型进行检测,并借助联合时频分析方法对信号进行处理。结果表明,外部天线超高频局部放电检测系统可以实现GIS局部放电检测,固定微粒局部放电频谱特征明显。 A new-type external antenna of ultra high frequency (UHF) partial discharge (PD) detection system is designed according to the wave-guide structure of gas-insulated metal-enclosed switch gear (GIS) and the wide band frequency spectral features of PD excited by electromagnetic waves. The fixed particle model of PD.in 252 kV GIS busbar is detected under the different voltage levels and the same SF6 pressure and then the joint time-frequency method (JTFA) is used to analyze these signals. The results indicate that this system can realize PD detection of GIS and the features of the fixed-particle PD can be obviously revealed.
出处 《电力系统自动化》 EI CSCD 北大核心 2004年第1期41-44,共4页 Automation of Electric Power Systems
基金 原国家电力公司科技项目
关键词 金属封闭式组合电器 GIS 局部放电 超高频检测 气体绝缘 光电法 化学气体分析法 gas-insulated metal-enclosed switch gear(GIS) partial discharge (PD) ultra-high-frequency (UHF) joint time- frequency analysis(JTFA)
  • 相关文献

参考文献4

二级参考文献6

  • 1韩小莲,冯允平,邱毓昌,陈锦清.气体绝缘组合电器中的局部放电及其测量[J].西安交通大学学报,1995,29(3):30-38. 被引量:3
  • 2Baumgartner R et al. Partial discharge part XI:PD in gas-insulated substations-Fundamental considerations. IEEE EIM, 1991,7(6):5.
  • 3Pearson J S et al. A continuous UHF monitor for gasinsulated substations, IEEE Trans EI,1991, 6(3):469.
  • 4Nichdas de Kock et al. UHF PD detection in gas-insulated switchgear-suitablity and sensitivity of the UHF method in comparison with the IEC 270 method.IEEE EIM,1996,12(6):20.
  • 5Zhang M C et al. Wide bandwidth sensor for PD measurement in GIS. 3rd Internatinal Conference of ECAAA, Xian China, 1996.
  • 6邱毓昌.用超高频法对GIS绝缘进行在线监测[J].高压电器,1997,33(4):36-40. 被引量:84

共引文献111

同被引文献159

引证文献12

二级引证文献246