摘要
通过理论分析、模拟计算和实际应用 ,指出在风机盘管加新风机组的空调一次泵冷冻水系统中 ,由于实际大多数建筑的新风机组水阀目前不控制 ,在这样的系统中如果直接对一次泵进行变频改造和取消冷机旁通管 ,不仅仍然能够满足室内的空调要求 。
Presents that the variable-speed single chilled water loop without chiller bypass line can be used in the air-conditioning systems where the terminals are fan-coil units and the water valves of the air-handling units are not controlled automatically.The results of the simulation and practical applications also approved this viewpoint.
出处
《制冷与空调》
2003年第1期25-31,共7页
Refrigeration and Air-Conditioning