水电机组定子绕组绝缘过低的成因分析与处理

Analysis and Treatment of Low Insulation of Stator Windings in Hydro-turbine Generator Units
在线阅读 下载PDF
导出
摘要 定子绕组绝缘过低是水轮发电机的重大安全隐患。根据某水电站机组定子绕组试验放电的现象和试验数据,结合水轮发电机的结构特点,判断定子绝缘过低主要原因是定、转子绕组绝缘受潮,并采取投加热器辅助空载烘干方法处理绝缘受潮,使机组绝缘恢复正常。实践效果表明了该方法的有效性。 Low insulation of stator windings is a major safety hazard for hydro-turbine generators.Based on the discharge phenomena and the test data from the stator winding tests of a hydro-turbine unit,and considering the structural characteristics of hydro-turbine generators,it is determined that the major reason for the low stator insulation is the damp of the stator and rotor winding insulation.Then,a non-load operation drying method assisted with heaters is adopted to treat and restore the damp insulation.The practical results verifies the effectiveness of the proposed method.
作者 谭东念 TAN Dongnian(Hubei Qingjiang Hydroelectric Development Co.,Ltd.,Yichang 443000,China)
出处 《水电与新能源》 2026年第2期73-75,85,共4页 Hydropower and New Energy
关键词 发电机 定子绕组 绝缘过低 受潮严重 空载运行 electric generator stator winding low insulation severe damp no-load operation