摘要
断路器位置开入是500 kV线路保护的重要开入量之一。文章以一起500 kV线路保护断路器位置开入异常为例,从回路电位、开入原理、规范、接线等方面进行分析,确定异常原因是接线错误引起边断路器C相跳闸位置异常,最终通过修改现场接线消除异常。并且针对本起断路器位置开入异常事件总结了后续消缺工作中的排查思路和方法,可为500 kV线路保护断路器位置开入异常处理提供指导。
The circuit breaker position input is one of the key inputs for 500 kV line protection.In this paper,an abnormal position input in a 500 kV line protection was analyzed from the aspects of circuit potential,input principles,specifications and wiring.It was found that the abnormality was caused by a wiring error,leading to an abnormal C-phase tripping position of the side switch.The abnormality was eliminated by correcting the on-site wiring.Troubleshooting methods were summarized to guide future handling of similar position input abnormalities in 500 kV line protection.
作者
陆嘉捷
赵耀
雍成思
陈瑛
LU Jiajie;ZHAO Yao;YONG Chengsi;CHEN Ying(State Grid Jiangsu Electric Power Co.,Ltd.,Liyang Power Supply Company,Liyang 213300,China;State Grid Jiangsu Electric Power Co.,Ltd.,Suzhou Power Supply Company,Suzhou 215000,China;State Grid Jiangsu Electric Power Co.,Ltd.,Yangzhou Power Supply Company,Yangzhou 225000,China)